Rohde & Schwarz FSH8 kit with accessories

Rohde & Schwarz FSH8 R&S 8.28 Spectrum Analyzer w/ Options: Tracking Gen, VSWR Bridge, K14, K40, K41, K42

Fluke VR1710 kit with accessories

Fluke VR1710 Single Phase Voltage Power Quality Recorder

Fluke 1743 Three Phase Power Quality Logger

$2,999.00
Availability: Out of stock
SKU
PL05

Condition: Refurbished / Calibrated

Warranty: 1 YEAR WARRANTY

Request a Quote for

Have Questions or doubts? Submit the following request and expect our detailed quote within 24 hours!

we are commited to win your business!

 Fluke 1743 Power Quality Logger

Assess power quality and conduct long-term studies with ease
Compact and rugged, the Fluke 1743 three-phase power quality loggers are everyday instruments for technicians who troubleshoot and analyze power distribution systems. Capable of simultaneously logging up to 500 parameters for up to 85 days and capturing events, the Fluke 1740 Series helps uncover intermittent and hard-to-find power quality issues.

Plug and play
All three 1740 Series loggers feature easy plug and play setup, for immediate use. The current probes are connected to the logger with a single plug. The instrument automatically detects, scales, and powers the probes using line power from the measured voltages. Once it is connected, logging begins with the touch of a single button!

Electrical shock protection
The Fluke 1740 loggers feature double insulated enclosures and accessories to help prevent electrical shock when coming into contact with blanket bus bars, terminals, or cables. They are also designed to meet the stringent safety standards for use in 600 V CAT III and 300 V CAT IV environments

Measure all power quality and power parameters
For basic power logging, the Fluke 1743 captures all relevant power parameters.


Features:
  • Plug and play:
    • Setup in minutes with automatic current probe detection and powering
  • Installs inside the cabinet:
    • Compact, fully insulated housing and accessories fit easily in tight spaces, next to live power
  • Monitors power for the long-term:
    • Data can be downloaded during recording without interruption
  • Measure voltage with premium accuracy:
    • IEC61000-4-30 Class-A compliant voltage accuracy (0.1 %)
  • Quickly validate quality of power:
    • Assess power quality according to EN50160 power quality standard, with statistical overview
  • Rugged and reliable:
    • Designed for everyday field use, with no moving parts

Applications:
Fluke Model 1743 is the IP65 water-proof model for logging the most common power parameters including V, A, W, VA, VAR, PF, energy, flicker, voltage events, and THD.
  • Disturbance analysis
    • Uncover root cause of equipment malfunction for later mitigation and predictive maintenance
  • Quality of service compliance
    • Validate incoming power quality at the service entrance
  • Power quality studies
    • Assess baseline power quality to validate compatibility with critical systems, before installation
  • Load studies
    • Verify electrical system capacity before adding loads
  • Energy and power quality assessment
    • Validate performance of facility improvements by quantifying energy consumption, power factor, and general power quality, before and after, improvements

Specifications:
General
Intrinsic error Refers to the reference conditions and is guaranteed for two years
Quality system developed, designed, and manufactured according to DIN ISO 9001
Reference conditions 23 °C ± 2 K; 74 °F ± 2 K , Vm = 230 V ± 10 %
50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
phase sequence L1, L2, L3
interval length: 10 minutes
Wye connection (L1, L2, L3 to N)
Power supply: 88 V to 265 V ac
 
Ambient conditions
Working temperature range -10 °C to 55 °C (14 °F to 131 °F)
Storage temperature range -20 °C to 60 °C (-4 °F to 140 °F)
Reference temperature range 23 °C ± 2 K (74 °F ± 2 K)
Relative humidity Class C2 acc. IEC 60654-1
Housing robust, fully insulated housing and accessories
Environmental protection IP65 as per EN60529
Safety IEC/EN 61010-1 600 V CAT III
300 V CAT IV, pollution degree 2
double insulation
Type test voltage 5.2 kV rms, 50 Hz/60 Hz, 5 s
EMC
Emission IEC/EN 61326-1, EN5502
Immunity IEC/EN 61326-1
 
Voltage and current measurement
Input voltage
Input range VI P-N max 480 V ac
Input range VI P-P max 830 V ac
Max. overload voltage 1.2 V
Input range selection By job programming
Connections P-P or P-N, 1- or 3-phase
Nominal voltage V = 999 kV with PTs and ratio
Input resistance App. 820 k? per chan. Lx-N Single phase (L1 or A, L2 or B, L3 or C connected): app. 300 k?
Intrinsic uncertainty 0.1 % of V
Voltage transformer Ratio: < 999 kV / V
Ratio selection By job programming
Current input with Flexi-Set
Input ranges II (L1 or A, L2 or B, L3 or C, N) 15 A/150 A/1500 A/3000 A ac
Measuring range 0.75 A to 3000 A ac
Intrinsic uncertainty < 2 % of I
Position influence Max. ± 2 % of measured value ヨ for distance conductor to meas. head > 30 mm
Stray field influence < ± 2 A ac for Iext = 500 A ac and distance to measuring head > 200 mm
Temperature coefficient < 0.05 %/K
Current transformer Ratio = 999 kA/I
Ratio selection By job programming
Connection 3-phase, 3-phase +N, 2 phase L1 or A and L3 or C (2 W-meter-method) 7 pole connector
Current input for clamp
Input ranges II (L1 or A, L2 or B, L3 or C, N) 0.5 V nominal (for II) 1.4 Vpeak
Intrinsic uncertainty < 0.3 % of I
Max. overload 10 V ac
Input resistance App. 8.2 k?
Current transformer Ratio = 999 kA/I
Ration selection By job programming
Power configurations Delta, 2-Element Delta, Wye, Single Phase, Split Single Phase
 
Logger
Power supply
Functional Range 88 V to 660 V absolute, 50 Hz/60 Hz
100 V to 350 V dc
Internal fuse: 630 mA T
Power consumption 5 Watts
Ride through 3 sec Capacitor
Fuse Power supply fuse can be replaced in service facility only. Supply can be connected in parallel to measuring inputs (up to 660 V)
Display, indicators LEDs for status and voltage levels
Memory Capacity 8 MB Flash-EPROM
Intervals A function > 12,000 intervals for > 85 days with 10 min intervals
P function > 30,000 intervals for > 212 days with 10 min intervals
Events > 13,000
Memory model Linear or circular
Interface USB and RS 232, 9600 to 115,000 Baud, automatic Baud rate selection, 3-wire communication
Dimensions 170 mm x 125 mm x 55 mm (69 in x 51 in x 22 in)
Weight approx. 2 kg (435 lb)
Measurement
A/D converter 16 bit, sample rate: 10.24 kHz
Anti-aliasing filter FIR-Filter, fC = 4.9 kHz
Frequency response Uncertainty < 1 % of Vm for 40 Hz to 2500 Hz
Interval length 1, 3, 5, 10, 30 s, 1, 5, 10, 15, 60 minutes
Averaging time for Min/max values ½, 1 mains period, 200 ms, 1 , 3 , 5 s
Time base Resolution: 10 ms (at 50 Hz), deviation: 2 s/day at 23 °C ± 2 °C (74 °F ± 2 °F)




For full Fluke 1743 specifications, please click here: Fluke 1743

Fluke 1743 Three-Phase Power Quality Logger

Compact and rugged, the Fluke 1743 three-phase power quality logger is an everyday instrument for technicians who troubleshoot and analyze power distribution systems

Fluke Model 1743 is the IP65 water-proof model for logging the most common power parameters including V, A, W, VA, VAR, PF, energy, flicker, voltage events, and THD

Includes Carrying Case & Accessories As Listed

Fluke 1743 Fluke-1743 Power Quality Logger Models On Sale Warranty Calibration Backed by The Best Service and Lowest Prices in the Industry.

BC# 17608-L/T*

  • Fluke 1743 Three-Phase Power Quality Logger (BC# 17608-L/T*)
  • Fluke 1735/174x 4 Phase Flexi Cable
  • (4) Fluke Dolphin Clips
  • International IEC Power Plug Adapter Set
  • 4GB USB Adapter
  • Fluke 1743 User's Manual
  • RS232 PC Interface Cable
  • Strap For Unit
  • Carrying Case