The i2000 is an AC current probe utilizing the Rogowski principle. It can be used to measure currents up to 2000A when used in conjunction with multimeters, recorders or data loggers. The flexible and lightweight measuring head allows quick and easy installation in hard to reach areas.
- Three ranges: 20A, 200 A & 2000 A, 100 mV/A, 10 mV/A & 1 mV/A output
- Ideal for current measurement on thick and hard to reach conductors without breaking the circuit
- Maximum conductor diameter 178 mm
- CAT III 600V safety rating
Specifications
Electrical specifications |
Current ranges |
|
Output sensitivity (AC-coupled) |
|
100 mV |
|
10 mV |
|
1 mV |
|
1 mV per A |
|
Load impedance |
|
Accuracy |
at +25 °C |
± 1 % of range (45 Hz to 65 Hz) |
|
Linearity |
10 % to 100 % of range |
± 0.2 % of reading |
|
Noise |
|
8 mV ac rms (30 A) |
|
2 mV ac rms (300 A, 3000 A) |
|
Frequency range |
|
Phase error |
|
< ± 1 º (45 Hz to 65 Hz) |
|
± 10 º (at 20 kHz) |
|
Position sensitivity |
with cable > 25 mm from the coupling |
± 2 % of range |
|
External field |
with cable > 200 mm from the head |
± 1 % of range |
|
Power supply |
|
2 x AA/MN 1500/LR6 Alkaline, 200 hours, low battery indicator |
|
Temperature Coefficient |
|
Working voltage |
see Safety standards section |
600 V AC rms or DC |
|
General Specifications |
Head Circumference |
|
Head cable diameter |
|
Head bend radius |
|
Cable length (head to electronics) |
|
Output connection |
|
Molded 4 mm safety plugs (not integrated) |
|
Operating temperature range |
|
0 °C to +70 °C (32 °F to 158 °F) (head and electronics) |
|
Storage temperature range |
|
-40 °C to +105 °C (-40 °F to 221 °F) (head) |
|
-20 °C to +85 °C (-4 °F to 185 °F) (electronics) |
|
Operating humidity |
|
15 % to 85 % (non-condensing) |
|
Weight |
|
180 g (6.34 oz) (head) |
|
190 g (6.70 oz) (electronics) |
|
Safety standards |
|
EN 61010-1: 2001 |
|
EN 61010-2-032: 2002 |
|
EN 61010-031: 2002 |
|
600 Vrms, Category III, Pollution Degree 2 |
|
Use of the probe on uninsulated conductors is limited to 600 V ac rms or dc and frequencies below 1 kHz. |
|
EMC standards |
|
EN 61326: 1998 +A1, A2, & A3 |
|
Dimensions |
HxWxD |
116 mm x 68.5 mm x 30 mm (4.56 in x 2.69 in x 1.18 in) |
|
Fluke i2000 Flex Flexible AC Current Probe
Current Ranges
- 20 A
- 200 A
- 200 A
- AC rms
Ideal For Current Measurement On Thick And Hard To Reach Conductors Without Breaking The Circuit
Fluke i2000Flex i2000-Flex Flexible AC Current Probe Models On Sale Warranty Calibration Backed by The Best Service and Lowest Prices in the Industry.