Hioki 3196 Power Quality Analyzer

 

  • Measure power factor
  • Sags
  • Swells
  • Flicker
  • Transients
  • Harmonics
  • High Frequency transient
  • Detection and waveform display
  • Four current and Four voltage channels

 

The 3196 POWER QUALITY ANALYZER is a highly advanced measuring instrument that can monitor and record abnormal phenomena related to power supply quality and analyze the causes of problems that lead to incorrect operation of electrical equipment. By simply connecting the 3196 to the power line to be monitored, you can accurately record the exact timing and types of power supply abnormalities that has occurred, and display a list of the events recorded.

An especially noteworthy feature of the 3196 is its gap-less recording capability (the ability to measure and record events continuously without loss of measurement data), which is necessary for analyzing the quality levels of factors such high frequency voltage, RMS voltage, power, 3-phase systems, harmonics as well as the power supply's K factor and flicker. The ability to instantly display details about items such as monitored waveforms simply by selecting them from an event list makes analysis easier. Although other instruments are available in the market for analyzing power supply quality, none of them have been capable of measuring all types of events simultaneously on a single instrument; this is what makes the 3196 such a notable development in supporting analysis of power supply problems.

Measurements can be taken from single-phase 2-wire, single-phase 3-wire, 3-phase 3-wire, or 3-phase 4-wire lines. Additional input channels are provided for voltage and current (one each), and support is provided for separate system measurement, DC voltage, and neutral wire measurement.

Up to one month of continuous measurement data can be recorded in internal memory. Further, data can be saved to a PC card (an ATA flash card of up to 528 MB) as well as to internal memory. The 3196 also comes equipped with an HTTP server function, eliminating the need for special-purpose interface applications and allowing you to use any general web browser (such as Internet Explorer) for full remote monitoring and control.

The 3196 POWER QUALITY ANALYZER is a state-of-the-art measuring instrument that serves as a powerful aid to resolving various kinds of power supply problems. The trend toward power liberalization has been accompanied by an increase in problems with power quality, resulting in a steady need for power quality analyzers. Recently, the rapid growth in use of electronic devices such as computers has been accompanied by an increase in problems with electronic systems in places such as factories and businesses, making monitoring of power supply problems a topic of increasing concern. Also, with the restructuring of the energy business (deregulation of power, sale of electricity, dispersed power supplies, and cogeneration), more countries are paying attention to power supply quality, and the importance of power supply quality analyzers has grown. The 3196 is the answer to these needs by being able to simply and faithfully capture power supply abnormalities and analyze various kinds of problems.



Applications
  • Power delivery - For businesses that supply and sell electricity (such as power companies): Maintenance and management of power supply quality, and cause analysis when power supply problems occur.
  • Power system facilities - For manufacturers of transformer equipment, electrical safety organizations, and electrical constructors: Evaluation and maintenance of power facilities, and periodic maintenance and power quality problem analysis during system operation.
  • Large electrical facilities - Evaluation and problem analysis for semiconductor manufacturing equipment, vending machines, OA equipment, UPS equipment, air conditioners, and welders.
  • Maintenance and inspection at factories - All types of power supply quality maintenance and problem analysis, such as power line maintenance and management at factories, maintenance and management of production equipment, energy conservation for ESCO businesses, building maintenance, maintenance and management of treatment equipment at clinics and hospitals, maintenance and management of communications equipment, etc.

 Specifications:

 
Operating environment PC/AT-compatible devices
OS English or Japanese versions of the following
Microsoft Windows 95 (9624 only, OSR2 or later versions only supported, Internet Explorer 3 or later required)
Microsoft Windows 98, Me, NT 4.0, 2000 or XP
Memory At least 128 MB
Power quality measurement standards conformance IEC61000-4-30:2003, IEEE1159, EN50160:1999
Clock functions Auto calendar, auto leap year, 24-hour clock
Real-time clock accuracy Within ±0.3 s/day (when the 3196 is turned on)
Internal memory capacity for data 13 MB (time series and event data)
Maximum recording interval 1 month (internal memory)
Measurement time control Manual/Specified time
Time series data settings
Recording item setting patterns
MAX/MIN/AVE values
Interval selections

Power, P&Harm, and ALL DATA
AVE values, ALL values (maximum, minimum, and average values)
1, 3, 15, or 30 seconds, 1, 5, 10, 15, or 30 minutes, 1 or 2 hours
Event settings
Event settings
Event threshold value setting
Maximum number of recording events

All measurement settings except flicker and inter-harmonics
OFF or desired numerical value
100 (internal memory) (Simultaneous events count as 1 event.
Power supply 12 V DC from the AC ADAPTER 9458 or BATTERY PACK 9459
Maximum rated power 40 VA
Continuous operating time with battery Approximately 30 minutes (Battery pack 9459)
External dimensions Approximately 298W (11.73") × 215H (8.46") × 67D (2.64") mm (not including projections)
Mass Approximately 2.25 kg (79.4 oz.) (including Battery pack 9459)
Input specifications
Measurement line types Single-phase 2-wire, Single-phase 3-wire, Three-phase 3- wire (3P3W2M, 3P3W3M) or Three-phase 4-wire, plus one extra input channel
Input channels
Voltage
Current

4 channels (U1 to U4) (channel U4 can be switched between AC and DC)
4 channels (I1 to I4)
Input methods Voltage between U1, U2, and U3 without inter-channel isolation
Voltage between U1 to U3 and U4 with inter-channel isolation
Current input by clamp-on sensor
Input resistance
Voltage
Current

4 MO ±10% (differential input)
200 kO ±10%
Measurement method Simultaneous digital sampling of voltage and current PLL synchronization (automatically switches to fixed clock during dropouts, so sampling is never interrupted)
PLL synchronization channel source Voltage at either U1, U2, or U3
PLL synchronization frequency range 42.5 to 69 Hz
Sampling frequency:
For calculations (including DC measurement)

For harmonic and inter-harmonic analysis


For transient overvoltage (impulse)

256 points/cycle
256 points/8 cycles (for 400 Hz)
2048 points/10 cycles (for 50 Hz)
2048 points/12 cycles (for 60 Hz)
2048 points/80cycles (for 400 Hz)
2 MHz
A/D converter resolution
For calculations (including DC measurement)
For transient overvoltage (impulse)

16 bits
12 bits
Voltage measurement range
Channels 1 to 3
Channel 4

150.00, 300.00, 600.00 Vrms
60.000, 150.00, 300.00, 600.00 Vrms
±60.000, 600.00 V pk (DC measurement)
Voltage crest factor 3 or less
Current measurement range
With Model 9694 sensor
With Model 9660 sensor
With Model 9661 sensor
With Model 9667 sensor
With Model 9669 sensor

5.0000, 50.000 Arms
50.000, 100.00 Arms
50.000, 500.00 Arms
50.000, 500.00 A or 500.00 A, 5.0000 kArms
100.00 A, 1.0000 kArms
Current crest factor 4 or less
Measurement specifications
RMS voltage
Measurement method True RMS (calculated continuously every 10 or 12 cycles at 50 or 60 Hz respectively)
Range selection Manual (channels 1 to 3 are set in the same operation)
Measurement accuracy AC : ±0.2% rdg. ±0.1% f.s.
DC : ±0.3% rdg. ±0.4% f.s.
RMS current
Measurement method True RMS (calculated continuously every 10 or 12 cycles at 50 or 60 Hz respectively)
Range selection Manual (channels 1 to 3 are set in the same operation)
Measurement accuracy ±0.2% rdg. ±0.1% f.s. + clamp-on sensor accuracy
Transient overvoltage (impulse)
Measurement method 2 MHz sampling
Measurement range 2000 Vpk
Display items 4 ms waveform (2 ms before and after center peak)
Period Period exceeding threshold (max. 4 ms)
Minimum detectable duration 0.5 µs
Measurement accuracy ±5.0% rdg. ±20 V (1000 V DC and 700 Vrms/100 kHz)
Voltage swell (rise in RMS voltage)
Measurement method True RMS (a single cycle is calculated by overlapping each half cycle) (The voltage between lines is measured for three phase 3-wire lines, and phase voltage is measured for three phase 4-wire lines.
Display items Amplitude and duration of swell
Measurement accuracy Same as RMS voltage
Voltage dip (drop in RMS voltage)
Measurement method True RMS (a single cycle is calculated by overlapping each half cycle) (The voltage between lines is measured for three phase 3-wire lines, and phase voltage is measured for three phase 4-wire lines.)
Display items Amplitude and duration of dip
Measurement accuracy Same as RMS voltage
Instantaneous Interruption
Measurement method Same as voltage dip
Frequency
Measurement range 42.500 to 69.000 Hz
Measurement source Voltage (same as the PLL synchronization source)
Measurement accuracy ±10 mHz (10 to 110% of range, with sine wave)
Active power
Measurement method Calculated continuously every 10 or 12 cycles at 50 or 60 Hz respectively
Measurement accuracy ±0.2% rdg. ±0.1% f.s. + clamp-on sensor accuracy
Reactive power
Measurement accuracy ±1 dgt. from the calculation of each measurement value (±3 dgt. for the sum)
Power factor
Measurement range -1.000 (lead) to 0.000 to +1.000 (lag)
Measurement accuracy ±1 dgt. from the calculation of each measurement value (±3 dgt. for the sum)
Displacement power factor
Measurement method Calculated from the phase difference between the fundamental waveforms of voltage and current
Measurement range -1.000 (lead) to 0.000 to +1.000 (lag)
Measurement accuracy ±0.5% rdg. ±0.2% f.s. ±1 dgt.(±3 dgt. for the sum)
Voltage unbalance factor
Measurement method Calculation for three-phase 3-wire (3P3W3M) and three phase 4-wire fundamental waveforms of voltage
Current unbalance factor
Measurement method Calculation for three-phase 3-wire (3P3W3M) and three-phase 4-wire fundamental waveforms of current
?V10 flicker
Display items ?V10, ?V10 (average over one hour, fourth maximum over one hour, maximum over one hour, overall maximum (during the measurement period)), ?U (deviation with respect to nominal voltage)
Standard voltage: Auto Same operation as AGC for IEC flicker
Measurement accuracy ±2% rdg
IEC flicker (short period flicker Pst, long period flicker Plt)
Measurement method Per IEC61000-4-15 Pst is measured for 10 minutes, and Plt is measured for 2 hours
Measurement accuracy ±5% rdg. or less of the limit value
Harmonic voltage, current and power (including fundamental waveform components)
Analysis window Rectangular
Analysis orders 1 to 50
Measurement accuracy
Voltage/current

Power

1st to 20th orders : ±0.5% rdg. ±0.2% f.s.
21st to 50th orders : ±1.0% rdg. ±0.3% f.s
1st to 20th orders : ±0.5% rdg. ±0.2% f.s.
21st to 30th orders : ±1.0% rdg. ±0.3% f.s.
31st to 40th orders : ±2.0% rdg. ±0.3% f.s.
41st to 50th orders : ±3.0% rdg. ±0.3% f.s
Inter-harmonic voltage and current
Analysis window Rectangular
Analysis orders 0.5 to 49.5
Harmonic voltage/current phase difference (including fundamental waveform content)
Measurement method Difference between voltage and current phase angle components
Display items Sum of all or multiple channels
Measurement accuracy 1st to 3rd orders : ±2°
4th to 50th orders : ±(0.02° × k+2°), k = harmonic order
Display specifications
Display device 6.4" TFT color LCD (640 × 480 dots)
Text display English, German, French, Italian, Spanish, Chinese or Japanese
External interface specifications
External control terminals External event input and output
PC card interface Slot Compliant with PCMCIA/JEIDA PC Card Standard,  Type II slot × 1
Compatible cards Flash ATA cards up to 528 MB
RS-232C interface
Standard
Destination device
Printer interval selections

EIA RS-232C-compliant (with 9-pin D-sub connector)
Printer or modem or GPS
OFF, 1, 5, 10, or 30 minutes, 1 or 2 hours
LAN interface
Communications protocol

Ethernet and TCP/IP (with 10BASE-T RJ-45 connector)
Environment & safety specifications
Operating environment Indoors, up to a height of 2000 m (6562.2 ft)
Storage temperature & humidity -20 to 50°C, max. 80% rh (non-condensating)
Operating temperature and humidity  0 to 40°C, max. 80% rh (non-condensating)
Maximum measurement terminal voltage
Voltage terminals
Current terminals

780 Vrms AC,  1103 V peak
1.7 Vrms AC, 2.4 V peak
Maximum in-phase voltage 600 Vrms AC (50/60 Hz, voltage input terminals)
Withstand voltage  5.55 kVrms AC/1 min  (50/60 Hz, 1 mA current sensitivity) Between voltage and clamp input terminals, between the voltage input terminal and 3196 casing, and between voltage input terminals (U1 to U3) and voltage input terminal (U4)
Enclosure protection IP30 (per EN60529)
Standards conformance
EMC
Safety
Voltage input unit

EN61326 CLASS A, EN61000-3-2 and EN61000-3-3
EN61010
Contamination Level 2, Measurement Category III



For full Hioki 3196 product specifications, please click here: Hioki 3196

Hioki 3196 Three Phase Power Quality Analyzer

Measure And Record Events Continuously Without Loss Of Measurement Data!

Measurements can be taken from single-phase 2-wire, single-phase 3-wire, 3-phase 3-wire, or 3-phase 4-wire lines.

Includes Hard Carrying Case & Accessories As Listed

Hioki 3196 Hioki-3196 Power Quality Analyzer Models On Sale Warranty Calibration Backed by The Best Service and Lowest Prices in the Industry.

 

BC# 41248-L/T*

  • Hioki 3196 Power Quality Analyzer (BC# 41248-L/T*)
  • Ethernet Cable
  • Hioki 5012 Flash Card w/ Adapter
  • AC Adapter/Charger
  • Power Cord
  • RS232 PC Interface Cable
  • User Manual On CD-ROM
  • Carrying Case (G)