Cellcorder CRT-400
The Cellcorder CRT-400 is Alber's newest handheld cell voltage and resistance tester. This exciting addition to Alber's test, diagnostic and trending products measures and records cell float voltage, internal cell resistance, and intercell connection resistance.
The Cellcorder cell resistance tester displays and records cell float voltage, internal cell resistance, and intercell connection resistance. A compatible hydrometer lets you transfer specific gravity and temperature data using the IR port. The high contrast, 128 x 64 pixel, backlit graphical display shows menus and test results. A fully charged Cellcorder can test for seven hours, and isolated operation helps ensure safety and makes the Cellcorder easy to move around. The Cellcorder performs even in high noise environments - without the need to disconnect the battery from service. Up to a 60 amp DC load (on 2V cells) is used to calculate internal cell resistance and intercell resistance. Circuitry rejects the 50Hz/60Hz ripple often troublesome to AC-based impedance and conductance meters.


System Measurements

ユ Float Voltage Readings
ユ NiCadメs to multicell modules (16V)
ユ Internal Cell Resistance Measurement
ユ Intercell Resistance Connection
ユ Intertier Resistance Connection



System Features

  • Float Voltage Readings - The Cellcorder measures the voltage applied during full float operation. The voltage range covers all cells or modules up to 20 volts, with accuracy to four full digits.
  • Internal Cell Resistance - Using a patented process, the Cellcorder applies a momentary load and calculates internal cell resistance by determining instantaneous voltage drop and load current. Algorithms make this measurement possible on cells floating on-line or off-line.
  • Intercell Resistance - The Cellcorder measures the resistance between two electrically connected cell terminals. The measurement consists of connector resistance and contact resistance at the points of connection to the cell terminals.
  • Auto Ranging - The Cellcorder automatically selects the correct voltage range, load resistor, and test time.
  • Data Extraction and Analysis - After testing, transfer data to the PC via Flash drive or IR interface. Trending software analyzes test data, displays results in graph or tabulated formats, and saves and prints reports. You may export reports in ASCII, Excel® or comma-delimited format so other programs can generate customized reports.



Specifications:

 
Display
Type: LCD - STN Reflective
Viewing Area: 2.619ヤ x 1.309ヤ
Resolution: Graphics LCD 128 x 64
Viewing Angle: 40°
Backlight: White LED
Memory
Type: USB Flash Drive
Storage Capability: 1MB per 71 strings with 256 cells
Data Retention: 10 Years
Communications
Infrared: PC interface for data transfer; Physical IrDA compliant for printer interface
Battery
Type: 4 cell - 8800 mAh lithium ion
Voltage: 4.2V
Charge Time: 8 Hours
AC Adapter
Input Voltage: 90 - 264VAC
Output Voltage: 5VDC
Output Current: 4.0 Amps
Frequency: 47 - 63HZ
Environmental
Operating Temp: : 0°C - 40°C (32°F - 104°F)
Storage Temp: : -29°C - 60°C (-20°F - 140°F);
For extended periods <25°C (<77°F)
Humidity Range: 0% to 80% RH (noncondensing) at 0°C - 31°C; 0% to 50% RH
(non-condensing) at 32°C - 40°C
Insulation Category II
Pollution Degree 2
Altitude: : 0 to 2000 meters above sea level
Packaging
305mm (12ヤ)H x 178mm (7ヤ)W x 76mm (3ヤ)D
Weight: 1.5Kg (3.4lbs)
Keypad: Rubber keys with polyurethane
coating
System Measurements
INPUT TEST CURRENT Voltage Resolution Intercell Range/Resolution
2V 50A 0.1% - ± 1mV 2mO± 2µO
4-6V 25-30A 0.1% - ± 3mV 3.3mO± 5µO
8-12V 30-35A 0.1% - ± 6mV 5mO± 10µO
16V 5A 0.1% - ± 10mV 20mO± 20µO



For full Alber CRT-400 product specifications, please click here: Alber CRT-400

Alber Cellcorder CRT-400 Cell Resistance Tester

The Cellcorder has multicell capability, it reads either single cells or multicell modules.

Includes Hard Carrying Case & Accessories As Listed

CRT400

Alber CRT-400 CRT400 Cell Resistance Tester Models On Sale Warranty Calibration Backed by The Best Service and Lowest Prices in the Industry.

 

BC# 44098-L/T*

  • Alber Cellcorder CRT-400 Cell Resistance Tester (BC#44098-L/T*)
  • Alber 1100-221 Test Lead Clamp Set
  • Alber 1100-222 Voltage Lead Assembly
  • AC Adapter/Charger
  • Power Cord
  • Strap For Unit
  • User Manual On CD-ROM
  • Hard Carrying Case
Request a Quote for

Have Questions or doubts? Submit the following request and expect our detailed quote within 24 hours!