Fluke 43B HandHeld Power Quality Analyzer Meter

Fluke i430 FLEXI-TF-II 6000 A Flexible AC Current Probe

Fluke i430 FLEXI-TF-II 6000 A Flexible AC Current Probe

Fluke 1730 Three Phase Energy Logger

$3,739.00
Availability: In stock
SKU
PL07

Condition: Refurbished

Warranty: 1 YEAR WARRANTY

Fluke 1730 Data Logger
The new Fluke 1730 Three-Phase Electrical Energy logger introduces a new simplicity to discovering sources of electrical energy waste. Discover when and where energy in your facility is being consumed; from the service entrance to individual circuits. Profiling energy usage across your facility helps you identify opportunities for energy savings, and provides you with the data you need to act on them. The new Energy Analyze software package allows you to compare multiple data points over time to build a complete picture of energy usage, which is the first step to reduce the cost of your energy bill.

Load studies
Discover how much energy individual pieces of equipment are consuming when they are operating at minimum and maximum capacity. Check capacity of circuits prior to adding additional loads (various standards exist for this process; in the US the NEC 220-87 is the recommended standard). Load studies can also identify situations where you may be exceeding the allowable load on the circuit or when an agreed peak demand applies from the utility. For convenience, some load studies simply measure current which makes installation of the measuring equipment quick and easy. It is often recommended that load surveys be performed for 30 days so that all typical load conditions are encountered during the test.

Energy surveys
Users often ask where measurements should be taken for an energy survey. The answer is multiple points within the facility. Start at the main service feeders; compare the power and energy measured here with the readings from the utility meter to ensure you’re receiving the correct charges. Then move downstream to the larger loads; these should be easy to identify by the current rating of the electrical panels downstream of the service entrances. Measuring at many points will allow a full picture of energy usage across the facility to be developed. The next question users typically have is how long an energy survey should last. This of course depends on the facility, but it is recommended that you measure for a period that matches a typical facility activity period. If the facility operates over a five day work week with down time on the weekend, a seven day survey will most likely capture typical conditions. If the facility operates at a constant level for 24 hours a day, 365 days a year, a single day could be reasonably representative as long as you avoid a period where there may be planned maintenance. To capture a full picture of the facilities energy usage it is not necessarily required to have measurements made simultaneously at every consumption point in the facility. To get a comprehensive picture, spot measurements can be made and then compared on a sliding time timescale. For example, you could compare the service entrance results from a typical Tuesday between 6:00 am and 12:00 pm with those of a larger load in the facility. Typically there will be some correlation between these profiles.

Power and energy logging
When a piece of equipment is operated it instantaneously consumes a specific amount of power in watts (W) or kilowatts (kW). This power is accumulated over the operating time and expressed as energy consumed in kilowatt hours (kWh). Energy is what your electric utility charges for; there will be a standard charge from the utility per kilowatt hour. Utilities may have other additional charges, such as peak demand, which is the maximum power demand over a defined period of time, often 15 or 30 minutes. There may also be power factor charges, which are based on the effects of the inductive or capacitive loads in the facility. Optimizing peak demand and power factor often results in lower monthly electricity bills. The 1730 Three Phase Electrical Energy logger has the capability to measure and characterize these effects enabling you to analyze the results and save money.

Simplified load studies
For situations where it’s either difficult or impractical to make a voltage connection the simple load study feature allows users to perform a simplified load study by measuring current only. The user can enter the nominal expected voltage to create a simulated power study. For accurate power and energy studies it is required to monitor both voltage and current but this simplified method is useful in certain circumstances.

Features:
  • Key measurements:
    • voltage, current, power, power factor and associated values enable energy saving strategies to be implemented.
  • Bright, color touch screen:
    • Perform convenient in-the-field analysis and data checks with full graphical display.
  • Comprehensive logging:
    • all measured values are automatically logged and can be reviewed during logging and before downloading for onthe-go analysis. More than 20 separate logging sessions can be stored on the instrument
  • Optimized user interface:
    • quick, guided, graphical setup ensures you’re capturing the right data every time, and the intelligent verification function indicates correct connections have been made, reducing user uncertainty.
  • Complete ‘in-the-field’ setup through the front panel:
    • no need to return to the workshop for download and setup or to take a computer to the electrical panel.
  • Wide range power:
    • power instrument directly from the measured circuit eliminating the need to find a power outlet while allowing the instrument to be secured safely inside electrical panels.
  • Two USB ports:
    • One for PC connection and another for fast, simple download to standard USB thumb drives, or other USB devices.
  • Compact size:
    • designed to fit in tight spaces and panels
  • Highest safety rating in the industry:
    • 600 V CAT IV/1000 V CAT III rated for use at the service entrance and downstream.
  • Optimized measurement accessories:
    • flat voltage cable and thin flexible current probes ensure easy installation even in tight spaces
  • Battery life:
    • four-hour operating time (backup time) per charge on lithium-ion battery.
  • Security:
    • safeguard against theft with a Kensington lock



Specifications:
Accuracy
Voltage Range Resolution Intrinsic Accuracy at Reference Conditions (% of Reading + % of Full Scale)
Current: Direct input iFlex1500-12 150 A
1500 A
0.1 A
1 A
± (1 % + 0.02 %)
± (1 % + 0.02 %)
iFlex3000-24 300 A
3000 A
1 A
10 A
± (1 % + 0.02 %)
± (1 % + 0.02 %)
 
iFlex6000-36 600 A
6000 A
1 A
10 A
± (1.5 % + 0.03 %)
± (1.5 % + 0.03 %)
i40s-EL clamp 4 A
40 A
1 mA
10 mA
± (0.7 % + 0.02 %)
± (0.7 % + 0.02 %)
Frequency 42.5 Hz to 69 Hz 0.01 Hz ± (0.1 %)
Aux input ± 10 V dc 0.1 mV ± (0.2 % + 0.02 %)
Voltage Min/Max 1000 V 0.1 V ± (1 % + 0.1 %)
Current Min/Max defined by accessory defined by accessory ± (5 % + 0.2 %)
Cos?/DPF 0 <= Cos? <=1 0.01 ± 0.025
Power factor 0 <= PF <=1 0.01 ± 0.025
THD on voltage 1000 % 0.1 % ± (2.5 % ± 0.05 %)
THD on current 1000 % 0.1 % ± (2.5 % ± 0.05 %)

Electrical Specifications:
Electrical specifications
Power supply
Voltage range 100 V to 500 V using safety plug input when powering from the measurement circuit
100 V to 240 V using standard power cord (IEC 60320 C7)
Power consumption Maximum 50 VA (max. 15 VA when powered using IEC 60320 input)
Efficiency ≥ 68.2 % (in accordance with energy efficiency regulations)
Maximum no-load consumption < 0.3 W only when powered using IEC 60320 input
Mains power frequency 50/60 Hz ± 15 %
Battery Li-ion 3.7 V, 9.25 Wh, customer-replaceable
On-battery runtime Four hours in standard operating mode, up to 5.5 hours in power saving mode
Charging time < 6 hours
Data acquisition
Resolution 16-bit synchronous sampling
Sampling frequency 5120 Hz
Input signal frequency 50/60 Hz (42.5 to 69 Hz)
Circuit types 1-?, 1-? IT, Split phase, 3-? delta, 3-? wye, 3-? wye IT, 3-? wye balanced, 3-? Aron/Blondel (2-element delta), 3-? delta open leg, Currents only (load studies)
THD THD for voltage and current is calculated using 25 harmonics
Averaging period User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
Demand interval User selectable: 5 min, 10 min, 15 min, 20 min, 30 min
Data storage Internal flash memory (not user replaceable)
Memory size Typical 20 logging sessions of 10 weeks with 10-minute intervals
Logging period Averaging period                                             Recommended for 20 sessions                                                                                  Logging Period for 1 session
1 second                                                                               3 hours                                                                                                                        2.5 days
5 seconds                                                                             15 hours                                                                                                                      12 days
10 seconds                                                                           28 hours                                                                                                                      24 days
30 seconds                                                                           3.5 days                                                                                                                      10 weeks
1 minute                                                                                7 days                                                                                                                         20 weeks
5 minutes                                                                              5 weeks                                                                                                                       2 years             
10 minutes                                                                            10 weeks                                                                                                                  > 2 years
15 minutes                                                                            3.5 months                                                                                                                > 2 years
30 minutes                                                                            7 months                                                                                                                   > 2 years
Interfaces
USB-A File transfer via USB flash drive, firmware updates Max. current: 120 mA
USB-mini Data download device to PC
Extension port Accessories
Voltage inputs
Number of inputs 4 (3 phases and neutral)
Maximum input voltage 1000 Vrms, CF 1.7
Input impedance 10 MΩ
Bandwidth (-3 dB) 2.5 kHz
Scaling 1:1, 10:1, 100:1, 1000:1 and variable
Measurement category 1000 V CAT III/600 V CAT IV
Current inputs
Number of inputs 3, mode selected automatically for attached sensor
Input voltage Clamp input: 500 mVrms/50 mVrms; CF 2.8
Rogowski coil input 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4; all at nominal probe range
Range 1 A to 150 A/10 A to 1500 A with thin iFlex flexible current probe, 12 inches
3 A to 300 A/30 A to 3000 A with thin Flex flexible current probe, 24 inches
6 A to 600 A/60 A to 6000 A with thin iFlex flexible current probe, 36 inches
40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL
Auxiliary inputs
Number of inputs 2
Input range 0 to ± 10 V dc, 1 reading/s
Scale factor (available 2014) Format: kx + d user configurable
Displayed units (available 2014) User configurable (7 characters, for example, °C, psi, or m/s)
Environmental specifications
Operating temperature -10 °C to +50 °C (14 °F to 122 °F)
Storage temperature -20 °C to +60 °C (−4 °F to 140 °F)
Operating humidity 10 °C to 30 °C (50 °F to 86 °F) max. 95 % RH
30 °C to 40 °C (86 °F to 104 °F) max. 75 % RH
40 °C to 50 °C (104 °F to 122 °F) max. 45 % RH
Operating altitude 2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV)
Storage altitude 12,000 m
Enclosure IP50 in accordance with EN60529
Vibration MIL 28800E, Type 3, Class III, Style B
Safety IEC 61010-1: Overvoltage CAT IV, Measurement 1000 V CAT III/600 V CAT IV, Pollution Degree 2
EMI, RFI, EMC EN 61326-1: Industrial
Electromagnetic compatibility Applies to use in Korea only. Class A Equipment (Industrial Broadcasting and Communication Equipment
Radio frequency emissions IEC CISPR 11: Group 1, Class A
Temperature coefficient 0.1 x accuracy specification/°C
General specifications
Color LCD display 4.3-inch active matrix TFT, 480 pixels x 272 pixels, resistive touch panel
Dimensions 1730: 19.8 cm x 16.7 cm x 5.5 cm (7.8 in x 6.6 in x 2.2 in)
Power supply: 13.0 cm x 13.0 cm x 4.5 cm (5.1 in x 5.1 in x 1.8 in)
1730 with power supply attached: 19.8 cm x 16.7 cm x 9 cm (7.8 in x 6.6 in x 3.5 in)
Weight 1730: 1.1 kg (2.5 lb)
Power supply: 400 g (0.9 lb)
External protection Holster, Kensington lock slot




For full Fluke 1703 specifications, please click here: Fluke 1703

Fluke 1730 Three Phase Energy Logger

Perform convenient in-the-field analysis and data checks with full graphical display

Includes Carrrying Case & Accessories As Listed!

Fluke 1730 Fluke-1730 Power Quality Logger Models On Sale Warranty Calibration Backed by The Best Service and Lowest Prices in the Industry.

 

BC# 42653-L/T*

  • Fluke 1730 Three Phase Energy Logger (BC# 42653-L/T*)
  • (3) Fluke iFlex 1500-12 Cables
  • Power Cord
  • USB PC Interface Cable
  • User Manual On CD-ROM
  • Carrying Case (G)