The Fluke 41B Harmonics Analyzer combines the ease of use of a digital multimeter, the visual feedback of an oscilloscope and the power of a harmonics analyzer in a single instrument. If you're testing power on three-phase systems or trouble-shooting harmonics on non-linear loads, no test tool makes it easier.


The Model 41B is ideal for further analyzing data and optimizing system performance. Use the Fluke 41B's FlukeView® software (included) to download acquired data to a printer or an MS-DOS® or Windows® compatible computer for analysis and presentation.

Features at a Glance


Three Views of each reading

  • Waveform
  • Bargraph showing harmonic levels
  • Numeric values

Real-time Display Updates

Display updates three times a second for a dynamic view of actual circuit conditions.

Comprehensive Measurements

Measure rms, peak and total harmonic distortion (THD) for complex voltages and currents - with no manual calculations required.

Three-Phase readings

From a simple single-phase measurement, automatically calculates three-phase power for 3-wire balanced loads (typically 5% or less imbalance). To make the single-phase measurement, simply connect the meter as shown and select the 3º, 3C watts display.

System Critical Data

Immediate readings of Power Factors, KVAR, Crest Factor, K-Factor.

Display Harmonics individually to the 31st

Min/Max and Average Recording

Data Storage

Up to eight complete measurement sets.

Isolated Serial Interface

Communications with a serial printer or DOS® or Windows®-compatible computer.

Safety Designed

To meet the latest standards: IEC 1010-1, pollution degree 2, Installation Category III, material group II, 600 V. Double insulated protection as described in IEC 1010-1, Annex H.

Volts

Display

One cycle of the fundamental waveform and its frequency. Instantaneous voltage at cursor position.

Application

Identifying sources of harmonic currents. Obtaining data for designing, specifying or sizing transformers, filters, etc.

Amperes

Display

%-fundamental or %-rms, rms value, frequency, and phase angle of fundamental or harmonic currents (up to 31st), as selected by cursor from bar graph.

Application

Identifying sources of harmonic currents. Obtaining data for designing, specifying or sizing transformers, filters, etc.

Watts

Display

Watts, volt-amps, power factor (total) and displacement power factor of fundamental of single-phase or three-phase power.

Application

Identifying displacement versus total power-factor. Determining proper power-factor correction methods.

Measurement Accuracy
Voltage
Range and Resolution: 5.0 V to 600 V rms (AC+DC); ±5.0 V to ±933 V peak
Accuracy: rms: ±(0.5 % + 2 digits); Peak or DC: ±(2 % + 3 digits) (Add 2 digits if < 15 V rms)
Current (1mV/A) Isolated input
Range and Resolution: 1.00 A to 1000 A rms (AC+DC); ±1.0 A to ±2000 A peak
Accuracy: rms: ±(0.5% + 3 digits)+probe specs; Peak or DC: ±(2 % + 4 digits) + probe specs
Watts/Volt-Amps (1mV/A) isolated input
Range and Resolution: 0.0W(VA) to 600 kW(kVA) average;
0.0W(VA) to ±2000 kW(kVA) peak
Accuracy: AC+DC: ±(1 % + 4 digits) + probe specs
Harmonics (harmonic level >5% using Smooth 20)
Volts: : Fundamental to 13th ±(2 %+2 digits);
At 31st ±(8 %+2 digits);
Amperes or Watts: Fundamental to 13th ±(3 % + 3 digits) + probe specs;
At 31st ±(8 % + 3 digits) + probe specs
Frequency
Range and Resolution: 6.0 Hz to 99.9 Hz
Accuracy: ±0.3 Hz
Input Bandwidth
DC, 6 Hz to 2.1 kHz
Crest Factor (CF)
Range and Resolution: 6.0 Hz to 99.9 Hz
Accuracy : ±0.3 Hz
Power Factor (PF)
Range and Resolution: 0.00 to 1.00
Accuracy: ±0.02
Displacement Power Factor (DPF)
Range and Resolution: 0.00 to 1.00
Accuracy: ±0.04 to ±0.03 (0.30 to 0.89) ±0.02 (0.90 to 1.00)
Phase
Range and Resolution: -179 º to 180 º
Accuracy (Fundamental): ±2 º + probe specs
K-Factor (KF)
Range and Resolution 1.0 to 30.00
Accuracy ± 10%
% THD-F
Range and Resolution: 0.00 % to 799.9 %
Accuracy: ±(0.03 Reading + 2.0 %)
% THD-R
Range and Resolution: 0.0 % to 99.9 %
Accuracy: ±(0.03 Reading + 2.0 %)

General Specifications
Minimum Input Levels
5 V rms or 1 A rms
Battery Life
4 alkaline "C" cells ANSI/NEDA-14A, IEC-LR14 (supplied) 48 hours typical (continuous)
Shock & Vibration
Per MIL-T-28800, Class 3
Case
Drip-Proof and Dust-Proof per IEC, IP 52
Size
234 mm L x 100 mm W x 64 mm D (9.2" L x 3.9" W x 2.5" D)
Weight
0.9 kg (2.0 lb.)




For full Fluke 41B product specifications, please click here: Fluke 41B

Fluke 41B HandHeld Power Harmonics Analyzer

Measure rms, peak and total harmonic distortion (THD) for complex voltages and currents - with no manual calculations required.

Includes Fluke 80i-500s AC Current Clamp, Carrying Case & Accessories As Listed

41 B

Fluke 41B Fluke-41B Power Harmonics Analyzer Models On Sale Warranty Calibration Backed by The Best Service and Lowest Prices in the Industry.

 

BC# 40373-L/T*

  • Fluke 41B Power Harmonics Analyzer (BC# 40373-L/T*)
  • Fluke 80i-500s AC Current Clamp
  • (2) 1000V Hard Point Test Leads
  • Carrying Case (G)
Request a Quote for

Have Questions or doubts? Submit the following request and expect our detailed quote within 24 hours!

we are commited to win your business!