AEMC 3945-B PowerPad 3Phase Power Quality Analyzer
Condition: Refurbished / Calibrated
Warranty: 1 YEAR WARRANTY
Shipping: USA & Worldwide
- AEMC 3945-B PowerPad Three-Phase Power Quality Analyzer (BC# 37860-L/T*)
- (4) AEMC Test Leads
- (4) AEMC Alligator Clips
- RS232 Interface Cable
- Power Cord
- Case For Unit
- Hard Copy User Manual
- Carrying Case (G)
AEMC 3945-B Three-Phase Power Quality Analyzer
Wouldn't it be nice if you could look inside your electrical system and see whatâ??s going on? Troubleshooting would be so much easier if you could see the volts, amps and harmonic content in real time and take pictures to document and analyze. Now you can do just that and more with AEMCâ??s PowerPad. The full color graphical display lets you see and analyze each signal clearly. Its high speed sample rate, at 256 samples per cycle, provides excellent fidelity in reproducing waveforms and capturing transients that happen as fast as 62.5µs.
PowerPadâ??s 4MB of memory is conveniently partitioned to let you store four different types of data, synchronized or independent of each other. You can store up to 12 screen snapshots, up to 50 captured transients that contain four cycles for each active input, and 4096 alarm events. You can also record trend data for days, weeks or even months.
Six direct access function buttons quickly let you see:
- Waveforms
- Display Volts, Amps, THD and Crest Factor by phase or for all phases. You can display all the voltage inputs on one screen, phase-to-phase or phase-to-neutral. Real-time phasor diagrams can be displayed for volts and amps, also by phase or for all phases
- Harmonics
- Display Harmonics out to the 50th for Volts, Amps and VA. Individual Harmonics are displayed as a percentage and in real value. Harmonic direction and sequencing can also be displayed.
- Transients
- Set, capture and display transients. You select the threshold and the number of transients to capture. PowerPad then captures four waveforms for each transient; the triggering waveform as well as one pre- and two post-triggered waveforms. As many as 1200 waveforms can be captured.
- Alarms
- Configure, capture and display up to 4096 alarm events based on up to ten different trigger variables. Each captured alarm event will show the phase, the variable and the value as well as the time and duration.
- Record
- Set up and record trend data at selectable rates from one sample/second to one sample every 15 minutes on as many as 22 different variables for all phases. See the recorded data on screen, zoom in and out and scroll the time axis to analyze the data.
- Power & Energy
- Display Watts, VARs and VA by phase and total. Accumulate totals and see whether the energy is inductive or capacitive.
If youâ??re not convinced yet, consider these other functions and features:
- PowerPad uses current probes that auto configure the instrumentâ??s current channel for range and scale.
- PowerPad comes with an online help system that gives you clear information about the functions and buttons for each screen.
- PowerPad speaks six different languages. At the press of a button, information can be displayed in English, Spanish, French, Portuguese, Italian and German.
Features:
- True RMS single-, two- and three-phase measurements at 256 samples/cycle, plus DC
- Real-time color waveforms
- Easy-to-use on-screen setup
- Automatic current probe recognition and scaling
- True RMS voltage and current measurement
- Measures DC volts, amps and power
- Display and capture voltage, current and power harmonics to 50th order, including direction, in real time
- Capture transients down to 1/256th of a cycle
- Phasor diagram display
- Peak voltage and current
- Nominal frequency from 40 to 70Hz
- VA, VAR and W per phase and total
- kVAh, VARh and kWh per phase and total
- Neutral current display for three-phase
- Crest factors for current and voltage
- Transformer K-factor display
- Power Factor, displacement PF display
- Captures up to 50 transients
- Short-term flicker display
- Phase unbalance (current and voltage)
- Harmonic Distortion (total and individual) from 1st to 50th
- Alarms, surges and sags
- Records date and characteristics of disturbances
- Immediate printout directly to a printer
- Screen snapshot function captures waveforms or other information on the display
- Optically isolated RS-23 communication port
- 600V Cat. IV safety rating
Applications:
- Verification of power distribution circuits
- Measurement and recording of power system quality (kW, VA, VAR)
- Energy metering (kVAh, VARh, kWh)
- In plant troubleshooting of power distribution panels and individual machinery
- Monitor pad mount transformers
- Determine harmonic problems originating from source or load
- Monitor phase unbalances
- Determine transformer K-factor
Specifications:
ELECTRICAL | |||
Sampling Frequency | 256 samples per cycle | ||
Data Storage | 4MB partitioned for waveforms, transients, alarms and trend recording | ||
Voltage (TRMS) | Phase-to-Phase: 960V Phase-to-Neutral: 480V | ||
Current (TRMS) | MN Clamp: 0 to 6A/120A or 0 to 240A SR Clamp: 0 to 1200A MR Clamp: 0 to 1000AAC,10 to 1400ADC AmpFlex®: 0 to 6500A1 |
||
MEASUREMENT | RANGE | RESOLUTION | ACCURACY |
Single-Phase RMS Voltages | 15 to 480V | 0.1V | ±0.5% ± 2cts |
Phase-to-Phase RMS Voltages | 15 to 960V | 0.1V | ±0.5% ± 2cts |
DC Voltage Component | 15 to 680V | 0.1V | ±1% ± 2cts |
Single-Phase Peak Voltages | 15 to 680V | 1V | ±(1% + 5cts) |
Phase-to-Phase Peak Voltages | 15 to 1360V | 1V | ±(1% + 5cts) |
Frequency (Hz) | 40 to 69Hz | 0.01Hz | ±0.01Hz |
Current Probes (Arms) MN Clamp SR Clamp AmpFlex® Probe |
0 to 240A 0 to 1200A 10 to 6500A |
0.1A 0.1A; 1A ≥ 1000A 0.1A; 1A ≥ 1000A |
±(0.5% + 2cts) ±(0.5% + 2cts) ±(0.5% + 1A) |
Active (Real) Power (kW) | 0 to 9999kW | 4 digits (10,000ct) | ±1% ± 1ct @ PF ≥0.8 |
Reactive Power (kVAR) | 0 to 9999kVAR | 4 digits (10,000ct) | ±1% ± 1ct @ PF ≤0.8 |
Apparent Power (kVA) | 0 to 9999kVA | 4 digits (10,000ct) | ±1% ± 1ct |
Power Factor (PF & DPF) | -1.000 to 1.000 | 0.001 | ±(1.5% + 0.01) |
Active Energy (kWh) | 0 to 9999MWh | 4 digits (10,000ct) | ±1% ± 1ct @ PF ≥0.8 |
Reactive Energy (kVARh) | 0 to 9999MVARh | 4 digits (10,000ct) | ±1% ± 1ct @ PF ≤0.8 |
Apparent Energy (kVAh) | 0 to 9999MVAh | 4 digits (10,000ct) | ±1% ± 1ct |
Unbalance (V & A) | 0 to 100% | 0.1% | ±1% ± 1ct |
Phase Angle (V–A, A–A, V–V) | -179° to +180° | 1° | ±2° ± 1ct |
Harmonics (1st to 50th) F = 40 to 69Hz (V ≥ 50V, A > Inom/100) |
0 to 999% |
0.1% |
±1% + 5cts |
Total Harmonic Distortion (V & A) | 0 to 999% | 0.1% | ±1% + 5cts |
K-factor (Akf) | 1 to 99.99 | 0.01 | ±5% ± 1ct |
Flicker (PST) | 0.00 to 9.99 | 0.01 | - |
Power Source | 9.6V NiMH rechargeable battery pack AC supply: 110/230VAC ±20% (50/60Hz) |
||
Battery Life | ≥8 hrs with display on; ≤35 hrs with display off (record mode) | ||
MECHANICAL | |||
Dimensions | 9.5 x 7 x 2" (240 x 180 x 55mm) | ||
Weight | 4.6 lbs (2.1kg) | ||
DISPLAY | |||
Display Type | 1/4 VGA (320 x 240) color LCD | ||
ENVIRONMENTAL | |||
Operating Temperature | 32° to 122°F (0° to 50°C) | ||
Storage Temperature | -4° to 122°F (-20° to +50°C) | ||
SAFETY | |||
Safety Rating | EN 61010-1, 600V Cat. IV2, Pollution Degree 2 | ||
Double Insulation | Yes | ||
CE Mark | Yes |