AEMC 5060 5000V 10 Tohm Digital Insulation Resistance Megohmeter
$3,395.00
Availability:
In stock
SKU
2H17
Condition: Refurbished / Calibrated
Warranty: 1 YEAR WARRANTY
Shipping: USA & Worldwide
- AEMC 5060 5000V 10 Tohm Digital Insulation Resistance Megohmeter (BC#: -L/T*)
- (3) Test Leads (1-Red 1-Blue 1-Black)
- Power Cord
- User Manual On CD-ROM
- Carrying Case
Request a Quote for
AEMC 5060 5000V 10 Tohm Digital Insulation Resistance Megohmeter
Features:
- True Megohmmeter
- Test voltage selections of (500, 1000, 2500, and 5000) V
- Variable test voltage from (50 to 5100) V (Model 5060)
- Variable test voltage from (50 to 5100) V (Model 5060)
- Automatic discharge at the completion of the test
- Measure AC voltage up to 4000 V
- Automatic test inhibit if live voltage detected above a set value
- Programmable alarms for all functions
- Automatic calculation of DAR, PI and DD ratios
- Large, backlit LCD screen with digital display and bargraph
- Measures capacitance up to 49.99 µf
- Stores up to 1500 measurements
Specifications:
| Test Voltage | 500V: 10 kΩ to 2000 GΩ (2 TΩ) 1000V: 10 kΩ to 4000 GΩ (4 TΩ) 2500V: 10 kΩ to 10,000 GΩ (10 TΩ) 5000V: 10 kΩ to 10,000 GΩ (10 TΩ) |
| User Selectable Test Voltage | Programmable: (40 to 1000) V: 10 V increments; (1000 to 5100) V: 100 V increments |
| Accuracy | 10 kΩ to 399.9 GΩ: ± 5 % of Reading ± 3 cts 400 GΩ to 10 TΩ: ± 15 % of Reading ± 10 cts |
| Voltage Test / Safety Check | 2500 Vac / 4000 Vdc |
| Voltage Warning Indicator | Yes > 25 V |
| Test Inhibition | Yes – selectable at (3, 10, or 20) % of test voltage |
| Smooth Function (user selectable) | Digital filtering stabilizes display readings |
| COMMUNICATION | |
| Storage of Readings over Time R(t) | 128 kB memory |
| Storage of Test Results | 1500 readings |
| Communication Port | USB optically isolated port |
| PC Software / Report Generation | DataView® (included) |
| ELECTRICAL | |
| Power Supply | (1) 9.6 V NiMH battery pack (included) Line power: (85 to 256) V (50 / 60) Hz |
| SAFETY | |
| Safety Rating | EN 61010-1, 600 V, CAT III 1000 V |