AEMC PEL 115 4 Channel Power & Energy Logger

AEMC PEL 115 4 Channel Power & Energy Logger

Fluke 561 thermometer

Fluke 561 Infrared and Contact Thermometer

AEMC OX5042B 3-in-1 Handscope Portable Harmonic Analyzer

$2,295.00
Availability: In stock
SKU
PH03

Condition: Refurbished / Calibrated

Warranty: 1 YEAR WARRANTY

Shipping: USA & Worldwide

  • AEMC OX5042B Portable Harmonic Analyzer (BC#: -L/T*)
  • (2) Test Leads
  • USB PC Interface Cable
  • Power Cord
  • User Manual On CD-ROM
  • Carrying Case
Request a Quote for

Have questions or doubts? Submit the following request and expect our detailed quote within 24 hours!

We are commited to win your business!

AEMC OX5042B 3-in-1 Handscope Portable Harmonic Analyzer
One of the few handheld oscilloscopes on the market with isolated channels

Features:

  • Two isolated channels
  • 40MHz oscilloscope
  • 2 Independent 8000-count TRMS Digital Multimeters
  • 3.5" color LCD screen with LED backlighting
  • Integrated interactive multilingual help function
  • 2MB recording data storage
  • Communication via isolated USB SCPI protocol

Specifications:

INTERFACE
Display 3.5" color TFT LCD screen; Resolution 320 x 240 – LED backlighting
Display mode 2500 real acquisition points on screen
Trace display 2 traces + 2 references + memory trace or mathematical calculation
Interactive Help Function 11 languages: French, English, German, Spanish, Italian, Swedish,
Romanian, Russian, Finnish, Polish, Dutch
OSCILLOSCOPE MODE
Bandwidth 40MHz
Bandwidth Limiter 1.5MHz, 5kHz
Number of Channels 2 totally isolated channels
Input Impedance 1MΩ ±0.5%, approx. 17pF
Maximum Input Voltage 600V CAT III – Derating -20dB per decade from 100kHz
Vertical Sensitivity 5mV to 200V/div
Sweep Speed 25ns/div to 200s/div – Roll Mode from 100ms to 200s/div
Horizontal Zoom Zoom factor: x1, x2, x5
Triggering Mode Automatic, triggered, one-shot & triggered Roll
Type Edge, pulse width (20ns – 20s)
Coupling AC or DC (depending on the coupling of the triggering channel) HF, LF or noise rejection
Sensitive ≤ 1.2 divisions p-p up to 40MHz
Maximum Sampling Rate 2GS/s in ETS mode – 50MS/s in one-shot mode on each channel
Vertical Resolution 9 bits
Memory Depth 2500 points per channel
User Storage 2MB
Glitch Mode Duration ≥ 20ns – 1250 min/max pairs
Display Modes Envelope, Averaging (factors 2 to 64) and XY (vector)
Math Functions Channel inversion, addition, subtraction, multiplication and division (adjustable scaling)
Cursor Measurement 2 cursors: V, T, dV, dt simultaneously – 4-digit display resolution
Automatic Measurement 18 time or level measurements and phase measurement
MULTIMETER MODE
General Specifications 2 channels, 8000-count display + min/max bargraph – Graphic recording of 2700 measurements (5min to 1 month)
Operating Modes Absolute or relative display (absolute, deviation, ref, ref%) – Monitoring (instantaneous, min, max, Avg)
AC, DC & AC+DC Voltages Ranges from 600mV to 600Vrms, 800mV to 800Vdc – accuracy for Vdc ±1% reading+20D –50kHz bandwidth
Resistance Range from 80Ω to 32MΩ - accuracy ±2% reading + 10D –10ms quick continuity test
Capacitance Ranges from 5nF to 5mF – basic accuracy ±2% reading + 10D
Other Measurements Frequency, rotation speed, 3.3V diode test, temperature measurement (with K-type thermocouple or infrared probe)
POWER
Measurements Single-phase and balanced three-phase active power values
HARMONIC ANALYZER MODE
Multi-Channel Analysis 2 channels, up to 31st harmonic fundamental frequency from 40 to 450Hz
Simultaneous Measurements Total VRMS, THD and selected order (% fundamental, phase, frequency, Vrms)
GENERAL
Screenshots Up to 100 in standard “.bmp” format, viewable on the instrument
PC Communication Isolated optical USB interface
Power Supply 6 LR6 or 6AA NiMh batteries – Battery life up to 8hrs 30min
Universal line adapter isolated from the channels – Quick charging in 2hrs 30min
Safety/EMC Safety according to IEC61010-1 Ed3 – 600V CAT III, EMC according to EN61000-3, 2001 & EN61326-1, 2006