Alber Cellcorder CRT-300 Cell Resistance Tester
Condition: Refurbished
Warranty: 1 YEAR WARRANTY
Shipping: USA & Worldwide
- Alber Cellcorder CRT-300 Cell Resistance Tester (BC# 43025-L/T*)
- Alber 1100-221 Test Lead Clamp Set
- Alber Voltage Lead Assembly
- AC Adapter/Charger
- Power Cord
- Strap For Unit
- User Manual On CD-ROM
- Hard Carrying Case
Alber Cellcorder CRT-300
Liebert offers the latest in battery monitoring technology with products by Albér ラ a leader in the field since 1972. Albér technologies by Liebert are designed to prevent battery failure, optimize useful battery life, reduce maintenance cost and increase safety.
The Albér Cellcorder CRT-300 Cell Resistance Tester
The Albér Cellcorder CRT-300 cell resistance tester displays and records cell float voltage, internal cell resistance and intercell connection resistance.
The portable unit is lightweight, rugged and durable. Standard features include a memory card, backlit graphical reflective LCD display for better contrast and specially designed cables and clamps with interchangeable jaws for different battery post designs. A built-in infrared port provides wireless communications to printer, PDA, DMA-35N Hydrometer or laptop computer.
Accurate Data in a Fraction of Normal Test Time
The Albér Cellcorder can be used on single cell or multicell modules. The memory card allows a virtually unlimited amount of data storage. The memory card, infrared port or optional internal modem transfers readings to a PC for analysis and report generation. Using a compatible hydrometer, you may also download specific gravity and temperature data to the Cellcorder using the wireless infrared port. The high contrast, 128 x 64 pixel, backlit graphical display shows menus and test results. A fully charged Cellcorder can test for seven hours while isolated operation helps ensure safety and makes the unit easy to move around.
System Capabilities:
- Float Voltage Readings
- The Cellcorder measures the voltage applied during full float operation. The voltage range covers all cells or modules up to 20 volts with accuracy up to four full digits.
- Internal Cell Resistance
- Using a patented process, the Cellcorder applies a momentary load and calculates internal cell resistance by determining instantaneous voltage drop and load current. Algorithms make this measurement possible on cells floating on-line or off-line.
- Intercell Resistance
- The Cellcorder measures the resistance between two electrically connected cell terminals. The measurement consists of connector resistance and contact resistance at the points of connection to the cell terminals.
- Auto Ranging
- The Cellcorder automatically selects the correct voltage range, load resistor, and time for a test.
- Reliable Readings
- The Cellcorder performs even in high noise environments - without the need to disconnect the battery from service. Up to a 60 amp DC load (on 2V cells) is used to calculate internal cell resistance and intercell resistance. Circuitry rejects the 50Hz/60Hz ripple often troublesome to AC-based impedance and conductance meters.
- Easy-To-Use
- Includes a combination keypad for alphanumeric data entry plus shift key for quick function keys. Interactive, multi-function menu buttons correlate to relevant menu selections on screen. A navigation key allows easy selection of choices in menu.
Specifications:
Physical | |
Dimensions | H 12ヤ (305mm) x W 7ヤ (178mm) x D 3ヤ (76mm) |
Weight | 3.4lb (1.5Kg) |
Keypad | Rubber keys with polyurethane coating |
Display | |
Type | LCD - STN Reflective |
Viewing Area | 2.619ヤ x 1.309ヤ |
Resolution | Graphics LCD 128 x 64 |
Viewing Angle | 40ヤ |
Backlight | White EL |
Memory | |
Type | Smart Media Card |
Supported Sizes | 8MB, 16MB, 32MB, 64MB and 128MB (8MB supplied) |
Storage Capacity | 71 strings with 256 cells per megabyte (8MB size card can store 568 strings) |
Data Retention | 10 years |
Communication | |
Infrared | Fully lrDA compliant for PDA/PC Interface. Physical IrDA compliant for printer interface. |
Battery | |
Type | 4 cell - 8800 mAh Lithium ion |
Voltage | 4.2V |
Charge Time | 8 hrs. |
AC Adapter | |
Input Voltage | 90-264 VAC |
Output Voltage | 5 VDC |
Output Current | 4.0 Amps |
Frequency | 47-63 Hz |
Environmental | |
Temperature Range: Operating |
0°C to 40°C (32°F to 104°F) |
Storage | -20°C to 60°C (-20°F to 140°F) |
Humidity Range | 0% to 80% RH (non-condensing) at 0°C to 31°C; 0% to 50% RH (non-condensing) at 32°C to 40°C |
Insulation Category II | |
Pollution Degree 2 | |
Altitude | 0 to 2000 meters above sea leve |
For full Alber CRT-300 product specifications, please click here: Alber CRT-300