Fluke 1550B Digital MegOhmMeter High Voltage Tester
Condition: Refurbished / Calibrated
Warranty: 1 YEAR WARRANTY
Shipping: USA & Worldwide
- Fluke 1550B Digital MegOhmMeter (BC# 34277-L/T*)
- (3) Fluke Test Cables
- Fluke USB Interface Cable
- Flukeview Forms Basic Software V3.0
- Power Cord
- User Manual On CD-ROM & Hard Copy
- Carrying Case w/ Strap
Fluke 1550B MegOhmMeter
The Fluke 1550B is a digital megohmmeter capable of testing switchgear, motors, generators and cables at up to 5000 V dc. It can be used for a wide range of tests: from simple spot checks to timed tests and breakdown tests. Measurement storage and PC interface software make it ideal for preventive maintenance.
Features
- Standard test voltages of 250 V, 500 V, 1000 V, 2500 V and 5000 V
- Additional test voltages available in 50 volt steps from 250 to 1000 volts, 100 volt steps from 1000 to 5000 volts
- Measures up to 1 Tera-Ohm
- Warning voltage function alerts the user that line voltage is present and gives the voltage reading up to 600 V ac or dc
- Automatic calculation of Dielectric Absorption and Polarization Index with no setup
- Guard system eliminates the effect of surface leakage current on high-resistance measurements
- Large digital/analog LCD delivers detailed measurement data
- Measures cable or insulation capacitance
- Measures leakage current
- Ramp function (0-5000 V dc) for breakdown testing
- 99 minute timer for timed tests
- Automatically stores test data in up to 99 locations that user can name for quick recall laterDatalogging
- Dielectric Absorption Ratio
- Insulation Test
- Live Circuit Detection
- Polarization Index
- Ramp Function
- Timer
The Fluke 1550B MegOhmMeter is the perfect tool for preventive maintenance, it includes everything electricians need to do their jobs quickly and easily
A digital megohmmeter capable of testing switchgear, motors, generators and cables at up to 5000 V dc.
The Fluke 1550B automatically calculates the polarization index and dielectric absorption ratios and combines insulation resistance testing up to 5000 V with measurement storage and PC interface software making it ideal for installation testing and preventive maintenance and commissioning.
The Fluke 1550B has the features you expect on higher-end testers, including a ramp function (0-5000 VDC) for breakdown testing, a timer for dielectric absorption, plus the ability to conduct leakage current and cable or insulation capacitance tests.
Easy to use with a simple interface, the meter provides insulation resistance testing up to 1 tera-ohm, with four output voltages: 500 V, 1000 V, 2500 V, 5000 V. The Fluke 1550Bメs warning voltage alerts notify the user that voltage is present and gives the voltage reading up to 600 V ac or dc.
With its large, fast-responding analog/digital display, The Fluke 1550B shows measurement changes graphically with easy-to-read analog bar graphs as well as digital measurements. Its 99 memory locations store all measurement parameters, which can then be downloaded to a Windows-based computer using the FlukeView Form software. The last-reading memory display is ideal for insulation resistance and lo-ohms.
The Fluke 1550B is powered by a high-capacity, rechargeable 12-volt battery that provides enough energy for up to 2,500 tests. In addition, the meter is fully tested to comply with EN 61010-1, CAT III 600 V overvoltage category , EN 61557 installation testing, and EN 61326 EMI immunity.
Specifications:
CAT III Rating | 600v |
Insulation Test Range | 0-1t? |
Test Voltages | 250 V, 500 V, 1000 V, 2500 V and 5000 V |
Power
Battery type | 12 volt, lead-acid, rechargeable |
Charger input (AC) | 85 to 250 V ac 50/60 Hz 50 VA |
Battery life (typical) Note: At higher temperatures, |
Test voltages Number of tests 250 V 4138 500 V 3913 1 kV 3462 2.5 kV 2043 5 kV 1000 |
Insulation resistance measurement
Test Voltage (dc) | Range | Accuracy (± reading) |
250 V | 200 kO to 5 GO 5 GO to 50 GO |
5 % 20 % |
500 V | 200 kO to 10 GO 10 GO to 100 GO |
5 % 20 % |
1000 V | 200 kO to 20 GO 20 GO to 200 GO |
5 % 20 % |
2500 V | 200 kO to 50 GO 50 GO to 500 GO |
5 % 20 % |
5000 V | 200 kO to 100 GO 100 GO to 1 TO |
5 % 20 % |
Range | Accuracy | |
Leakage current | 1 nA to 2 mA | ± (5 % + 2 nA) |
Capacitance measurement | 0.01 uF to 15.00 µF | ± (15 % rdg + 0.03 µF) |
Live circuit indicator |
30 V to 600 V ac/dc, 50/60 Hz |
± (5 % + 2 V) |
For full Fluke 1550B product specifications, please click here: Fluke 1550B