Fluke 1555 MegOhmMeter Insulation Resistance Tester
$5,995.00
Availability:
In stock
SKU
F1554
Condition: Refurbished / Calibrated
Warranty: 1 YEAR WARRANTY
Shipping: USA & Worldwide
- Fluke 1555 10 kV Digital MegOhmMeter Insulation Tester (BC# 30607-L/T*)
- (3) Fluke Voltage Clamps
- (3) Fluke Test Leads
- (3) Fluke Alligator Clips
- (2) Fluke Test Pins
- Fluke Interface Cable
- FlukeView Forms Basic Version 3.6 Software
- Power Cord
- User Manual On Cd-ROM
- Hard Copy User Manual
- Hard Carrying Case
Request a Quote for
Fluke 1555 Insulation Tester
The Fluke 1555 offers digital insulation testing up to 10 kV, making it ideal for testing high voltage equipment including switch gear, motors, and cables.
Evaluate the trends, eliminate the doubt
The Fluke 1555 insulation resistance tester offers digital insulation testing up to 10 kV, making them ideal for testing a wide range of high voltage equipment including switchgear, motors, generators and cables.
Fluke insulation testers can now conduct the entire range of test voltages specified in IEEE 43-2000 with a best in class, 3 year warranty and CAT IV 600 V safety rating. With measurement storage and PC interface, the 1555 is the perfect tool for preventive or predictive maintenance programs designed to identify potential equipment failures before they occur.
Features:
For full Fluke 1555 product specifications, please click here: Fluke 1555
The Fluke 1555 offers digital insulation testing up to 10 kV, making it ideal for testing high voltage equipment including switch gear, motors, and cables.
Evaluate the trends, eliminate the doubt
The Fluke 1555 insulation resistance tester offers digital insulation testing up to 10 kV, making them ideal for testing a wide range of high voltage equipment including switchgear, motors, generators and cables.
Fluke insulation testers can now conduct the entire range of test voltages specified in IEEE 43-2000 with a best in class, 3 year warranty and CAT IV 600 V safety rating. With measurement storage and PC interface, the 1555 is the perfect tool for preventive or predictive maintenance programs designed to identify potential equipment failures before they occur.
Features:
- Test voltages to up 10 kV and save time by trending on the spot only with Fluke Connect
- CAT III 1000 V, CAT IV 600 V safety rating
- Warning function alerts the user that line voltage is present and gives the voltage reading up to 600 V AC or DC for increased user safety
- Selectable test voltages in 50 V steps from 250 V to 1000 V, and 100 V steps above 1000 V
- Measurements can be stored in up to 99 memory locations, with each location assigned a unique, user defined, label for easy recall
- Long battery life gives the user over 750 tests between charges
- Automatic calculation of Dielectric Absorption (DAR) and Polarization Index (PI) with no additional setup
- Guard system eliminates the effect of surface leakage current on high-resistance measurements
- Large digital/analog LCD for easy viewing
- Capacitance and leakage current measurement
- Ramp function for breakdown testing
- Resistance measurements up to 2 TΩ
- Timer settings up to 99 minutes for timed tests
Electrical Specifications | The tester's accuracy is specified for one year after calibration at operating temperatures of 0°C to 35°C. For operating temperatures outside the range (-20°C to 0°C and 35°C to 50°C), add ±.25% per °C, except on the 20% bands add ±1% per °C. |
Insulation Resistance Measurement | |
Test voltage (DC) 250 V |
Range: < 250 kΩ, 250 kΩ to 5 GΩ 5 GΩ to 50 GΩ > 50 GΩ Accuracy (± reading): Unspecified 5% 20% Unspecified |
500 V | Range: < 500 kΩ 500 kΩ to 10 GΩ 10 GΩ to 100 GΩ > 100 GΩ Accuracy (± reading): Unspecified 5% 20% Unspecified |
1000 V | Range: < 1 MΩ 1 MΩ to 20 GΩ 20 GΩ to 200 GΩ > 200 GΩ Accuracy (± reading): Unspecified 5% 20% Unspecified |
2500 V | Range: < 2.5 MΩ 2.5 MΩ to 50 GΩ 50 GΩ to 500 GΩ > 500 GΩ Accuracy (± reading): Unspecified 5% 20% Unspecified |
5000 V | Range: < 5 MΩ 5 MΩ to 100 GΩ 100 GΩ to 1 TΩ > 1 TΩ Accuracy (± reading): Unspecified 5% 20% Unspecified |
10000 V | Range: < 10 MΩ 10 MΩ to 200 GΩ 200 GΩ to 2 TΩ > 2 TΩ Accuracy (± reading) U:nspecified 5% 20% Unspecified |
Bar graph range | 0 to 2 TΩ (1555) |
Insulation test voltage accuracy | -0%, +10% at 1 mA load current |
Induced AC mains current rejection | 2 mA maximum |
Charging rate for capacitive load | 5 seconds per μF |
Discharge rate for capacitive load | 1.5 s/μF |
Leakage current measurement | Range: 1 nA to 2 mA Accuracy: ±(5% + 2 nA) |
Capacitance measurement | Range: 0.01 μF to 15.00 μF Accuracy: ±(15% rdg + 0.03 μF) |
Timer | Range: 0 to 99 minutes Resolution Setting: 1 minute Resolution indication: 1 second |
Live circuit warning | Warning range: 30 V to 660 V AC/DC, 50/60 Hz Voltage accuracy: ±(15% + 2 V) |
General Specifications | |
Display | 75 x 105 mm |
Power | 12 V lead-acid rechargeable battery, Yuasa NP2.8-12 |
Charger Input (AC) | 85 V to 250 V AC 50/60 Hz 20 VA (This Class II (double insulated) instrument is supplied with a Class 1 (grounded) power cord. The protective earth terminal (ground pin) is not connected internally. The extra pin is for added plug retention only.) |
Dimensions | 269 x 277 x 160 mm (10.6 x 10.9 x 6.3 in) |
Weight | 3.7 kg (8.2 lb) |
Temperature (operating) | -20°C to 50°C (-4°F to 122°F) |
Temperature (storage) | -20°C to 65°C (-4°F to 149°F) |
Humidity | 80% to 31°C decreasing linearly to 50% at 50°C |
Altitude | 2000 m |
Enclosure sealing | IP40 |
Input overload protection | 1000 V AC |
Electromagnetic compatibility | EN 61326 |
Safety compliance | IEC 61010-1: Overvoltage category II, Pollution Degree 2. IEC 61010-2-030: Measurement 600V CAT IV / 1000V CAT III IEC 61557-1, IEC 61557-2 |
For full Fluke 1555 product specifications, please click here: Fluke 1555