Fluke 1621 GEO Earth Ground Resistance Tester Kit
$1,119.00
Availability:
In stock
SKU
2G05
Condition: Refurbished / Calibrated
Warranty: 1 YEAR WARRANTY
Shipping: USA & Worldwide
- Fluke 1621 Geo Earth / Ground Tester (BC# 42105-L/T*)
- User Manual On CD-ROM
- Carrying Case (G)
Request a Quote for
Fluke 1621 Earth Ground Tester
The Fluke 1621 is an easy-to-use earth ground tester. For ground resistance testing, the 1621 is the first line of defense in detecting reliable ground connections, the unit features basic ground testing methods including 3-pole Fall-of-Potential as well as 2-pole ground resistance. Its convenient size, rugged holster, and large, clear LCD display make it an ideal field earth tester, for most work environments. With a simple user interface and intuitive functionality, the Fluke 1621 is a handy tool for electrical contractors, utility test engineers, and earth ground specialists.
Features:
Specifications:
For full Fluke 1621 specifications, please click here: Fluke 1621
The Fluke 1621 is an easy-to-use earth ground tester. For ground resistance testing, the 1621 is the first line of defense in detecting reliable ground connections, the unit features basic ground testing methods including 3-pole Fall-of-Potential as well as 2-pole ground resistance. Its convenient size, rugged holster, and large, clear LCD display make it an ideal field earth tester, for most work environments. With a simple user interface and intuitive functionality, the Fluke 1621 is a handy tool for electrical contractors, utility test engineers, and earth ground specialists.
Features:
- 3-pole Fall-of-Potential earth testing for basic measurements
- 2-pole resistance measurements for added versatility
- Easily capture values with single-button operation
- Ensure accurate measurements with automatic ムnoiseメ voltage detection
- Hazardous voltage warning offers increased user protection
- Clearly read and record data with a large, backlit display
- Rugged holster and design for tough work environments
- Portable size allows for easy transportation
- Instantly be alerted to measurements outside of your set limit, when you use the adjustable limit setting
Specifications:
General specifications | |
Measuring functions | 3-pole earth ground resistance, 2 pole ac resistance of a conductor, Interference voltage |
Intrinsic error | Refers to the reference temperature range and is guaranteed for one year |
Measuring rate | 2 measurements/second |
Battery | One 9 volt alkaline (LR61) |
Battery condition | LO-BAT is displayed if voltage drops below 6.5 V |
Voltages | Between jacks H/C2 and E/C1: 250 Veff maximum (effective voltage) |
Between jacks S/P2 and E/C1: 250 Veff maximum | |
Climatic class | VDE/VDI 3540 RZ (conforming to KWG as per DIN 40040, 4/87) |
Temperature performance | Working: -10 °C to +50 °C (+14 °F to +122 °F) Operating: 0 °C to +35 °C (+32 °F to +95 °F) Storage: -20 °C to +60 °C (+68 °F to +140 °F) Reference: +23 °C ± 2 °C (+73 °F ± 4 °F) |
Temperature coefficient | ± 0.1 % of range per degree Kelvin |
Safety | IEC/EN 61010-1, 600 V CAT II, pollution degree 2 |
Dimensions | 113 mm x 54 mm x 216 mm (4.5 in x 2.1 in x 8.5 in.), including holster |
Weight | 850 g (1.9 lb), including standard accessories, volume approximately 600 cm |
Electrical specifications | ||
Parameter | Influence factor | Deviation influence |
E1 | Position | 0 % |
E2 | Supply voltage | 0 % |
E3 | Temperature E3 | 2.3 % |
E4 | Serial interference voltage (20 V) | 0.6 % |
E5 | Probe- and auxiliary probe resistance | 10 % |
Test voltage | 3.7 kV | |
Protection type | IP 40; IEC/EN 60529 | |
Electromagnetic compatibility | Emission: IEC/EN 61326 Class B Immunity: IEC/EN 61326 Annex C |
RE resistance measurement | ||||
Measuring method | Current-voltage measurement with improved cross-talk attenuation, no compensation of measuring lead resistance, with probe (3-pole) or without probe (2-pole), as per IEC/EN 61557-5 |
|||
Open circuit voltage | 23 to 24 V ac | |||
Short circuit current | > 50 mA ac | |||
Measuring frequency | 128 Hz | |||
Maximum permissible overload | 250 Veff | |||
Measuring range | Resolution | Display range | Intrinsic uncertainty | Operating uncertainty IEC 61557 |
0.15 O to 20 O | 0.01 O | 0 to 19.99 O | ± (6 % of measured value + 5D) | ± (18 % of measured value + 5D) |
200 O | 0.1 O | 20 to 199.9 O | ||
2 kO | 1 O | 200 to 1999 O | ||
Measuring time | 8 seconds (average from when START is pressed) | |||
Limit input | Tester retains set value even if instrument is turned off (assuming battery power supply is sufficient) |
Automatic changeover of resolution | |
RH | Resolution |
< 7 kO | 0.01 O |
< 50 kO | 0.1 O |
> 50 kO | 1 O |
Interference voltage display dc + ac | |
Vmax | 30 Veff |
Common mode rejection | > 80 dB at 50 Hz and 60 Hz |
Ri | 680 kO |
Measuring uncertainty | < 10 % for pure ac and dc signals |
For full Fluke 1621 specifications, please click here: Fluke 1621