Fluke 1664 FC Multifunction Installation Tester

Reduce test time up to 40% with Auto Test
Auto Test does 5 required installation tests in one sequence, including selectable Type A, AC & RCD Auto Test, ensuring compliance with local installation regulations. It reduces the number of manual connections, decreases the possibility of making errors and reduces test time up to 40% from previous Fluke models.

Insulation PreTest
Protect the installation. Avoid costly mistakes. The Fluke 1664 FC Installation Tester is the only installation with “Insulation PreTest,” which warns you about potentially serious and costly mistakes. If the tester detects that appliances are connected to the system during test, it will stop the insulation test and provide a visual and audible warning. This helps eliminate accidental damage to peripheral equipment and keeps your customers happy

Fluke Connect®, ShareLive™ calling and Fluke Cloud™ storage
Share from anywhere Save time—eliminate data entry by wirelessly syncing measurements directly from your installation tester and share with your team using the Fluke Connect system. Having access to measurements simultaneous at the inspection site and from the office or an off-site location enables faster decision making and real time collaboration between team members.

Fluke Cloud™ storage
Retrieve stored results from anywhere Cloud storage allows you to retrieve stored results whether you are in the office or in the field to make decisions in real time. Fluke Connect uses radio-enabled test tools and a mobile app to transfer measurements straight from the field to a secure cloud location, where the data can be accessed by team members. Plus you can import the data into Fluke DMS to process and generate certificates.

Key product capabilities
The 1660 Series testers verify the safety of electrical installations in domestic, commercial and industrial applications. They can ensure that fixed wiring is safe and correctly installed to meet the requirements of IEC 60364 and all relevant local standards.

Fluke 1664 FC
The Fluke 1664 FC is the only installation tester that protects connected appliances from damage during insulation tests, and allows you to share your test results wirelessly by smartphone with coworkers or customers. Fluke’s patent pending Insulation PreTest stops you from performing tests with appliances that are connected to the system during test. This helps eliminate accidental damage and keeps your customers happy. In addition, the Fluke 1664 FC offers you the power of Fluke Connect. Now you can send test results straight from your Fluke 1664 FC to your smartphone, and transmit those results to other members of your team. You can get feedback, suggestions and even have work orders sent to your job site. You can also save your test results to Fluke Cloud™ storage. No more writing down data on paper with the possibility of transcription errors. Cloud storage gives you a fast, secure and accurate way to storing all your test data and create test certificates with Fluke DMS.

Features:
  • Insulation-PreTest™ safety function
  • Insulation at L-N, L-PE, N-PE inputs
  • Auto Test sequence
  • Loop and line resistance—mΩ resolution
  • Continuity at L-N, L-PE, N-PE inputs


Specifications:
General Specifications
Size 10 cm (L) x 25 cm (W) x 12.5 cm (H)
Weight (incl. batteries) approx. 1.3 kg
Battery size, quantity 1.5 V type AA (IEC LR6), 6 pcs.
Sealing IP 40
Safety Complies with IEC/EN61010-1, UL61010, ANSI/ISA –s82.02.01 and CAN/CSA c22.2 No. 1010
Overvoltage CAT III 500 V, CAT IV 300 V
Performance EC/EN61557-1 to IEC/EN61557-7 and IEC/EN61557-10
AC and DC voltage measurement trms
Range 500 V
Resolution 0.1 V
Input Impedance 3.3 MΩ
Overload Protection 660 V rms
Continuity testing (RLO)
Range (Autoranging) 20 Ω/200 Ω/2000 Ω
Resolution 0.01 Ω/0.1 Ω/1 Ω
Open Circuit Voltage > 4 V
Insulation resistance measurement (RISO)
Test voltages 1663/1664 FC
100-250-500-1000 V 50-100-250-500-1000 V
50V
 
Insulation Resistance Range: 20 MΩ/50 MΩ
Resolution: 0.01 MΩ/0.1 MΩ
Test Current: 1 mA @ 50 kΩ
100 V

 
Insulation Resistance Range: 20 MΩ/100 MΩ
Resolution: 0.01 MΩ/0.1 MΩ
Test Current: 1 mA @ 100 kΩ
250 V Insulation Resistance Range: 20 MΩ/200 MΩ
Resolution: 0.01 MΩ/0.1 MΩ
Test Current: 1 mA @ 250 kΩ
500 V Insulation Resistance Range: 20 MΩ/200 MΩ/500 MΩ
Resolution: 0.01 MΩ/0.1 MΩ/1 MΩ
Test Current: 1 mA @ 500 kΩ
1000 V Insulation Resistance Range: 20 MΩ/200 MΩ/1000 MΩ
Resolution: 0.01 MΩ/0.1 MΩ/1 MΩ
Test Current: 1 mA @ 1 MΩ
Insulation pretest
Insulation safety pretest Requires to connect the Tester to L, N and PE.
Loop and line impedance (ZI )
Range 10 Ω (Hi current mΩ mode)/20 Ω/200 Ω/2000 Ω
Resolution 1 mΩ/ 0.01 Ω/ 0.1 Ω/1Ω
Prospective earth fault current, PSC test
Range 1000 A/10 kA (50 kA)
Resolution 1 A/0.1 kA
Computation: Prospective Earth Fault Current (PEFC) or Prospective Short Circuit Current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively.
RCD testing, RCD types tested
RCD Type AC1
G2, S3
Model 1664 FC A/F, AC, B/B+5, G, S
RCD trip time test (ΔT)
Current Settings1 10-30-100-300-500-1000 mA – VAR
10-30-100 mA
Multiplier x ½, x 1
x 5
Measurement Range
RCD Type G

RCD Type S

310 ms
50 ms
510 ms
160 ms
RCD trip current measurement/ramp test (I ΔN)
Current Range 30 % to 110 % of RCD rated current1
Step Size 10% of IΔN 2
Dwell Time
Type G
Type S

300 ms/step
500 ms/step
Measurement Accuracy ± 5 %
Notes
30 % to 210 % for Type A IΔN = 10mA
20 % to 210 % for Type B
Specified trip current ranges (EN 61008-1):
50 % to 100 % for Type AC
35 % to 140 % for Type A (>10 mA)
35 % to 200 % for Type A (≤10 mA)
50 % to 200 % for Type B
Earth resistance test (RE) Model 1664 FC and 1663 only
Range 200 Ω/2000 Ω
Resolution 0.1 Ω/1Ω
Frequency 128 Hz
Output Voltage 25 V
Phase sequence indicaton
Icon Phase Sequence indicator is active
Range 100 to 500 V
Display “1-2-3”: or “3-2-1”



For full Fluke 1664 product specifications, please click here: Fluke 1664