Fluke BT521 Advance Battery Analyzer 0.09% + 5 Accuracy BT 521
Condition: Refurbished / Calibrated
Warranty: 1 YEAR WARRANTY
Shipping: USA & Worldwide
- Fluke BT521 Advance Battery Analyzer : (BC# -L/T*)
- BTL10 Test Leads
- AC Adapter/Charger
- USB PC Interface Cable
- User Manual On Cd-ROM
- Soft Carrying Case(G)
Fluke BT521 Advance Battery Analyzer
The new Fluke 500 Series Battery Analyzer is ideal test tool for maintenance, troubleshooting and performance testing of individual stationary batteries and battery banks used in critical battery back-up applications.
Key Measurements:
- Battery resistance
- DC and AC voltage
- DC and AC current
- Ripple Voltage
- Frequency
- Battery temperature
Sequence measurement mode:
Automatic or manual sequence testing of battery strings with automatic measurement storage including voltage, resistance and temperature (with BTL21 intelligent test probe).
Comprehensive Logging:
All measured values are automatically captured during testing and can be reviewed on the instrument before downloading.
Optimized user interface:
Quick, guided setup ensures you’re capturing the right data every time, and the combined visual and audio feedback cues reduce the risk of measurement confusion.
Threshold comparison:
Configure multiple reference values and thresholds for resistance and voltage. Comparison result feedback after each measurement via visual and verbal cues.
Ergonomic test leads:
Rugged coaxial two pole kelvin test pins with remote SAVE button reduce test time and increase efficiency.
Specifications:
Functions | Range |
Resolution | Accuracy |
Battery resistance/ Strap resistance |
3 mΩ | 0.001 mΩ | 1 % + 8 |
30 mΩ | 0.01 mΩ | 0.8 % + 6 | |
300 mΩ | 0.1 mΩ | 0.8 % + 6 | |
3000 mΩ | 1 mΩ | 0.8 % + 6 | |
Vdc |
6 V | 0.001 V | 0.09 % + 5 |
60 V | 0.01 V | 0.09 % + 5 | |
600 V | 0.1 V | 0.09 % + 5 | |
1000 V | 1 V | 0.09 % + 5 | |
Vac (45 Hz to 500 Hz with 800 Hz filter) | 600 V | 0.1 V | 2 % + 10 |
Frequency (displayed with Vac and Aac) | 500 Hz | 0.1 Hz | 0.5 % + 8 |
AC voltage ripple (20 KHz Max) | 600 mV | 0.1 mV | 3 % + 20 |
6000 mV | 1 mV | 3 % + 10 | |
Adc/Aac (with accessory Fluke i410) | 400 A | 1 A | 3.5 % + 2 |
Temperature | 0 °C to 60 °C | 1 °C | 2 °C (4 °F) |
Meter mode | 999 records for each measurement position with time stamp | ||
Sequence mode | Up to 100 profiles and 100 profile templates (Each profile stores up to 450 batteries) with time stamp |