Fluke 1742 Three Phase Power Quality Logger Analyzer
Condition: Refurbished / Calibrated
Warranty: 1 Year Warranty
Shipping: USA & Worldwide
- Fluke 1742 Three-Phase Power Quality Logger (BC# 51032)
- (4) i17xx-flex1500IP 24 inch current probes
- (2) Alligator Clips (Blue)
- (4) Alligator Clips (Black)
- Voltage test lead (3-phase + N)
- MA-C8 Power Adapter
- (4) Test Leads
- Wifi Adapter
- USB PC Interface Cable
- Strap For Unit
- Carrying Case
Fluke 1742 Power Quality Logger
The Fluke 1742, 1746 and 1748 Three-Phase Power Quality Loggers give you fast, easy access to the data you need to make critical power quality and energy decisions in real-time.
Compact and rugged, the Fluke 1740 Series Three-Phase Power Quality Loggers are designed specifically for technicians and engineers who need the flexibility to troubleshoot, quantify energy usage and analyze power distribution systems. Fully compliant with international power quality standards such as IEC 61000-4-30 and capable of simultaneously logging up to 500 parameters while also capturing events, the Fluke 1740 Series helps uncover intermittent and hard-to-find power quality issues more easily than ever. The included Energy Analyze plus software quickly assesses the quality of power at the service entrance, substation, or at the load, according to national and international standards like EN 50160 and IEEE 519.
An optimized user interface, flexible current probes, and an intelligent measurement verification function that allows you to digitally verify and correct connections makes setup easier than ever and reduces measurement uncertainty. Minimize your time in potentially hazardous environments and reduce the hassle of suiting up in PPE by using a wireless connection (WiFi) to view data directly in the field.
Hardware features
- Measure all three voltage and current phases plus the neutral current: Three-phase and neutral voltage leads and four flexible current probes.
- Comprehensive logging: More than 20 separate logging sessions can be stored in the instrument. A comprehensive range of power and power quality variables are automatically logged so you never lose measurement trends.
- Measure with premium accuracy: Meets the rigorous IEC 61000-4-30 Class A Edition 3 standard for ‘Testing and measurement techniques—Power quality measurement methods.
- Capture dips, swells and interruptions: The 1748 includes event waveform capture and RMS event profile, along with date, timestamp and severity information to help pinpoint potential root causes of power quality issues.
- Measure key power quality parameters: Measures harmonics and interharmonics for voltage and current, also includes unbalance, flicker and rapid voltage changes.
- Optimized user interface: Capture the right data every time with quick, guided, graphical PC based application setup and reduce uncertainty about your connections with an intelligent verification feature and the only auto-correction function for a power quality logger. Connection errors are automatically indicated via an amber light on the units power button which turns green once corrected.
- Flexible power supply: Powers directly from the measured circuit with the widest available range for a power quality logger automatically going from 100 V to 500 V or from a wall line cord, so you can test anywhere.
- Rugged and reliable: Designed to withstand harsh installation environments with IP65 rating when used with IP65 voltage input adapter.
- Two external USB ports: One for PC connection and another for quick, simple data download to standard USB thumb drives, or other USB devices, allowing you to leave the measurement device in place without disrupting logging.
- Ethernet connectivity: Wired and wireless connections for instrument setup and highspeed data download.
- Compact size: Designed to fit in tight spaces and panels with small 23 cm x 18 cm x 5.4 cm (9.1 in x 7.1 in x 2.1 in) footprint.
- Highest safety rating in the industry: 600 V CAT IV/1000 V CAT III rated for use at the service entrance and downstream.
Specifications:
| Parameter | Range | Maximum Resolution | Intrinsic Accuracy at Reference Conditions (% of Reading +% of Range) | ||
| Voltage | 1000 V | 0.1 V | ±0.1 % of nominal voltage 1, 2 | ||
| Current: Direct input | i17xx-flex 1500IP 24 1500 A | 150 A | 0.01 A (min. 1.5A)3 | ±(1% + 0.02%) | |
| 1500 A | 0.1 A | ||||
| i17xx-flex 3000IP 24 3000 A | 300 A | 0.01 A (min. 3.0 A)3 | ±(1% + 0.03%) | ||
| 3000 A | 0.1 A | ||||
| i17xx-flex 6000IP 36 6000 A | 600 A | 0.01 A (min. 6.0 A)3 | ±(1.5% + 0.03%) | ||
| 6000 A | 0.1 A | ||||
| i40s-EL clamp | 4 A | 1 mA | ±(0.7% + 0.02%) | ||
| 40 A | 10 mA | ||||
| Frequency | 42.5 Hz to 69 Hz | 0.01 Hz | ±(0.1%)2 | ||
| Auxiliary input | ±10 V dc | 0.1 mV | ±(0.2% + 0.02%) | ||
| Voltage min/max | 1000 V | 0.1 V | ±0.2 % of nominal input voltage1 | ||
| Current min/max | Defined by accessory | Defined by accessory | ±(5% + 0.2%) | ||
| THD on voltage | 1000% | 0.10% | ± 2.5% | ||
| THD on current | 1000% | 0.10% | ± 2.5% | ||
| Voltage harmonics 2nd to 50th | 1000 V | 0.1 V | ≥ 1 V: ±5% of reading | ||
| < 1 V: ±0.05V | |||||
| Current harmonics 2nd to 50th | Defined by accessory | Defined by accessory | ≥ 3% of current range: ±5% of reading | ||
| < 3% of current range: ±0.15% of range | |||||
| Flicker PLT, PST | 0 to 20 | 0.01 | 5% | ||
| Current probe accuracy | |||||
| Parameter | Influence quantity | iFlex1500IP-24 | iFlex3000IP-24 | iFlex6000IP-36 | i40S-EL | 
| 150 A / 1500 A | 300 A / 3000 A | 600 A / 6000 A | 4 A / 40 A | ||
| Active Power P | PF ≥ 0.99 | 1.2% + 0.005% | 1.2% + 0.0075% | 1.7% + 0.0075% | 1.2% + 0.005% | 
| Active Energy Ea | |||||
| Apparent power S | 0 ≤ PF ≤ 1 | 1.2% + 0.005% | 1.2% + 0.0075% | 1.7% + 0.0075% | 1.2% + 0.005% | 
| Apparent Energy Eap | |||||
| Reactive power Q | 0 ≤ PF ≤ 1 | 2.5% of measured apparent power | |||
| Reactive Energy Er | |||||
| Power Factor PF | - | ±0.025 | |||
| Displacement Power | |||||
| Factor DPF/cosΦ | |||||
| Additional uncertainty in% of range | VP-N>250 V | 0.015% | 0.023% | 0.023% | 0.015% | 
 
     
     
         
            