IDEAL 61-806 Three Phase Power Quality Analyzer
$2,995.00
Availability:
In stock
SKU
PQ25
Condition: Refurbished / Calibrated
Warranty: 1 YEAR WARRANTY
Shipping: USA & Worldwide
- IDEAL 61-806 Power Quality Analyzer (BC# 21350-L/T*)
- (4) IDEAL CPR-1000 Clamps (BC# 21351-L/T* 21352-L/T* 21353-L/T* 21354-L/T*)
- IDEAL 61-806 Power Supply Adapter
- RS232 Communication Cable
- (4) Alligator Clips
- IDEAL Harmonics Program Adapter P/N: 275824
- Battery Pack
- Power Cord
- RS232 PC Interface Cable
- User Manual On CD-ROM
- Hard Carrying Case
Request a Quote for
IDEAL 61-806 Power Quality Analyzer
The IDEAL Power Analyzer. The most versatile and easy-to-use power quality test instrument on the market. Four programs measure and analyze power quality on both singleand three-phase electrical systems. Instantaneous readouts including tables, bar graphs and even individual waveforms make job site data interpretation easy. With a real-time clock and 1 MB of memory, the Power Analyzer stores data that can be downloaded to a personal computer for in-depth analysis using PowerVisionル Software.
The Energy and Harmonics Program comes standard with the IDEAL Power Analyzer. Disturbances, Check-Meter and Fast-Check Programs are available separately. These programs allow the user to monitor additional facets of power quality with a single test instrument. The details of each program are discussed on the opposite page.
Everything a professional needs for monitoring and analysis in a single unit. Rugged, versatile and loaded with features including computer compatibility. There have always been test instruments that help make the job easier, but the IDEAL Power Analyzer has taken power quality analysis to a new level.
Features:
Power Measurements:
For full IDEAL 61-806 specifications, please click here: IDEAL 61-806
The IDEAL Power Analyzer. The most versatile and easy-to-use power quality test instrument on the market. Four programs measure and analyze power quality on both singleand three-phase electrical systems. Instantaneous readouts including tables, bar graphs and even individual waveforms make job site data interpretation easy. With a real-time clock and 1 MB of memory, the Power Analyzer stores data that can be downloaded to a personal computer for in-depth analysis using PowerVisionル Software.
The Energy and Harmonics Program comes standard with the IDEAL Power Analyzer. Disturbances, Check-Meter and Fast-Check Programs are available separately. These programs allow the user to monitor additional facets of power quality with a single test instrument. The details of each program are discussed on the opposite page.
Everything a professional needs for monitoring and analysis in a single unit. Rugged, versatile and loaded with features including computer compatibility. There have always been test instruments that help make the job easier, but the IDEAL Power Analyzer has taken power quality analysis to a new level.
Features:
- Single- or three-phase measurements
- True RMS
- Data logging (1MB memory)
- Auto ranging
- Min/max/avg
- Energy and Harmonics Program
- Lightweight, portable design
- Easy-to-use push-button operation
- Password protected on-screen setup
- 160 x 160 pixel LCD
- RS-232 interface
- Customized data collection
- Real-time clock
- Programmable trigger-points and start/stop time
- Auto display shutoff
- Rechargeable Ni-Cad battery
- Intelligent battery charging system
Power Measurements:
- Kilowatts (kW)
- Voltamperes (VA)
- Inductive reactive power (kvarL)
- Capacitive reactive power (kvarC)
- Power factor (PF)
- Frequency (Hz)
- Kilowatt hours (kWh)
- Reactive power per hour (kvarhL, kvarhC)
- Total harmonic distortion (%THD)
- Harmonic factorization to 51st harmonic
Supply voltage: | 80-256VAC |
Frequency: | 50-60 Hz |
Burden: | 8 VA |
Operation Temperature | 0 to 50 °C |
Measuring circuit: | 3F 3-wire, 3F 4-wire, 3PT-2CT, 1F, 1F Split |
Safety: | Category II - 600 V, as per EN 61010 |
Internal memory: | 1 MB |
RS-232 output: | Serial type output |
Baud rate: | 1200, 2400, 4800, 9600, 19200, 38400 (user selectable) |
Voltage measurement: | |
Measuring range: | 20-500 VAC (phase-neutral) 20-866 VAC (phases-phase) |
Frequency: | 45-65 Hz |
Current measurement: | |
Phase current range: | 15-1000AAC ( Based on supplied clamp adapter. ) |
Neutral current range: | 1.5-100AAC ( Catalog #61-807 supplied with 100AAC clamp adapter. ) |
Accuracy: | |
Voltage: | 0.5 % of readout ± 2 digits |
Current: | 0.5 % of readout ± 2 digits |
Active power: | 1.0 % of readout ± 2 digits |
Reactive power: | 1.0 % of readout ± 2 digits |
Measuring conditions to assure accuracy: | - Temperature range between 5 ºC and 45 ºC - Power factor between 0.5 and 1 - Measuring range between 5 % and 100 % |
Mechanical Specifications: | |
Display: | 160 x 160 pixel backlit display |
Case dimensions: | 220 x 60 x 130 mm |
Weight | 0.8 kg |
Relevant Standards: | EN 60664,EN 610110, EN 61036, VDE 110, UL 94 |
For full IDEAL 61-806 specifications, please click here: IDEAL 61-806