Megger S1-1052 10 kV High Current Insulation Resistance Tester
Condition: Refurbished / Calibrated
Warranty: 1 Year Warranty
Shipping: USA & Worldwide
- Megger S1-1052 10kV Insulation Resistance Tester (BC# -L/T*)
- 3M Lead Set
- RS232 PC Interface Cable
- USB PC Interface Cable
- User Guide On CD-ROM
Megger S1-1052 Insulation Resistance Tester
The new 5 & 10 kV insulation resistance testers from Megger are designed specifically to assist you with the testing and maintenance of high voltage electrical equipment. IEEE 43-2000 recommends the use of 10 kV for motor windings rated above 12 kV and the Megger S1-1052 facilitates this. The case is incredibly rugged and easy to carry, being made of tough polypropylene and achieving an ingress protection rating of IP65. In addition, the model number is marked on both sides of the case for ease of identification in stores or vehicles.
The instruments have a large easy to read backlit LCD display making it equally suitable for use in both bright sunlight and poorly lit environments. Information displayed includes resistance, voltage, leakage current, capacitance, battery status and time constant. In addition, the elapsed time of the test is displayed constantly, removing the need for separate timers. Adjustable timers and limit alarms are included.
The instrument can test when being powered by the mains or its internal rechargeable battery, a great benefit when site conditions are unknown or long term testing is required.
The controls of the instrument are clear and unambiguous and a "quick start" guide is included in the lid of the instrument removing the need to carry bulky manuals under site conditions.
The instrument is fitted with a guard terminal to enhance accuracy. The guard test lead is included as standard with the instrument.
To further enhance the flexibility of the instruments both have the facility to set the test voltage in steps from 50 V to the maximum output voltage avoiding the expense of several insulation resistance testers to meet your application needs.
These IR instruments are designed to meet the highest safety standards and meet the requirements of EN61010. In addition, the instrument measures the voltage at the terminals and if this is above 50 V then the instrument will display the high voltage warning and inhibit testing. At the end of the test the instrument will automatically discharge the energy transferred to the equipment during the test phase.
The S1-552 and S1-1052 are equally suited to routine testing and diagnostic regimes being pre-programmed with IR, PI, DAR, SV and DD profiles.
Specifications:
Voltage input range | 85-265 V rms, 50/60Hz, 60 VA |
S1-1052 battery life | 4 hours continuous testing at 10 kV |
S1-1052 test voltages | 50 V to 1 kV in 10 V steps, 1 kV to 10 kV in 25 V steps |
S1-1052 accuracy (23ºC, 10 kV) | ±5% to 2 TΩ ±20% to 20 TΩ |
Guard | 2% error guarding 500 kΩ leakage with 100 MΩ load |
Display range | Digital display (3 digits) 10 kΩ to 15 TΩ (S1-552) to 35 TΩ
(S1-1052) Analogue display 100 kΩ to 1 TΩ |
Short circuit/charge current | 5 mA @ 5 kV ( S1-552) or 10 kV (S1-1052) |
Capacitor charge time | <3 seconds per µF at 5mA to 10 kV |
Capacitor discharge time | <250ms per µF to discharge from 10000 V to 50 V |
Capacitance measurement (above 500 V) | 10 nF to 50 µF (dependent on measurement voltage) |
Capacitance measurement accuracy (23°C) | ±5% ±5 nF |
Voltage output accuracy (0°C to 30°C) | +4%, -0%, ±10 V of nominal test voltage at 1 GΩ load |
Current measurement range | 0.01 nA to 5 mA |
Current measurement accuracy (23°C) | ±5% ±0.2 nA at all voltages |
Interference rejection | 1 mA per 600 V up to a maximum of 2 mA |
Timer range | Up to 99 minutes and 59 seconds from start of test 15 second minimum setting for test voltage ≥1000 V 30 second minimum setting for test voltage <1000 V |
Memory capacity | 32kB |
Test regimes | Auto IR, PI, DAR, SV and DD. |
Interface | RS232 and USB |
Data store | Voltage, test time, leakage current, resistance, PI, DAR, DD, capacitance and time constant |
Real time output | Serial, once per second of test voltage, current and resistance |
Operating temperature | -10°C to 50°C |
Storage temperature | -25°C to 65°C |
Ingress protection (lid closed) | IP65 |
Humidity | 90% RH non-condensing at 40°C |
Safety | Meets the requirements of EN61010-1:2001 CATIII 300 V |
EMC | Meets the requirements of EN61326-1:1998 for use in heavy industrial areas |
Dimensions | 305 x 194 x 360 mm (12.7 x 6 x 14.2 inches) |
Weight | 7.1 kg (16lb) approx. |