Megger S1-568 5 kV DC Insulation Resistance Tester
$4,229.00
Availability:
In stock
SKU
MG15
Condition: Refurbished / Calibrated
Warranty: 1 Year Warranty
Shipping: USA & Worldwide
- Megger S1-568 5kV DC Insulation Resistance Tester (BC# -L/T*)
- Test Lead Set
- Power Cord
Request a Quote for
Megger S1-568 Insulation Resistance
Tester
Megger’s new S1-Series of insulation resistance testers consist of a 5 kV, 10 kV and 15 kV models called S1-568, S1-1068 and S1-1568. These top end instruments are targeted at power utilities and service companies working in generation, transmission and distribution markets. Class leading charge current, noise rejection and software filters make the S1-Series Megger’s most advanced DC insulation resistance testers to date.
Instrument productivity is a focus of the new S1-Series which offers rapid charge batteries and operation from an AC source when the battery is flat. An intuitive user interface ensures no lost time remembering how to use the tester. Simplicity of operation is achieved with two rotary switches and a large backlight display which enables multiple results to be displayed simultaneously. A graphical quick start guide is provided inside the lid of each model to assist first time users.
Safety of operation is built in, 5 kV and 10 kV models are safety rated to CAT IV 600 V up to 3000 m and the 15 kV S1-1568 is rated at CAT IV 1000 V up to 4000 m. Original equipment manufacturers and repairers will welcome the remote control feature allowing them to automate resistance testing on the factory floor, as will technicians in substations wanting to operate from a more convenient, safe distance.
he S1-Series have a dual case design with a tough outer case to protect the tester from knocks and drops and a fire retardant inner case. The case IP rating prevents moisture and dust ingress when storing or carrying the instrument. The lids have clip-on lead pouches ensuring that leads remain with the instrument at all times. Case lids are removable for improved access to the terminals.
Five preset voltage ranges are provided in insulation test mode, plus a user settable lock voltage range. Preconfigured diagnostic tests include Polarisation Index (PI), Dielectric Absorption Ratio (DAR), Dielectric Discharge (DD), Stepped Voltage (SV) and Ramp test.
Advanced memory storage includes time/date stamping of results, logging of data and recall of results to screen. A fully isolated USB interface or on-board Bluetooth® interface is used for safe transfer of data to Megger’s asset management software; PowerDB Pro, Advanced or Lite packages.
Test leads are double insulated with clamps rated at 3 kV tequivalent to 6 kV single insulation for the medium clip leadset and 5 kV t equivalent to 10 kV single insulation for the large clip. The 15 kV leadset is insulated to 15 kV.
APPLICATION
The Insulation Resistance (IR) test is a quantitative test which indicates the effectiveness of a product’s electrical insulation. Applications include cables, transformers, motors/generators, circuit breakers and bushings. Common insulation tests are the “spot test”, a 1 minute IR test and a 10 minute Polarisation Index (PI) test, where PI is the ratio R10min / R1min and is temperature independent.
Features and benefits
For full Megger S1-568 Insulation Tester product specifications, please click here: Megger S1-568
Megger’s new S1-Series of insulation resistance testers consist of a 5 kV, 10 kV and 15 kV models called S1-568, S1-1068 and S1-1568. These top end instruments are targeted at power utilities and service companies working in generation, transmission and distribution markets. Class leading charge current, noise rejection and software filters make the S1-Series Megger’s most advanced DC insulation resistance testers to date.
Instrument productivity is a focus of the new S1-Series which offers rapid charge batteries and operation from an AC source when the battery is flat. An intuitive user interface ensures no lost time remembering how to use the tester. Simplicity of operation is achieved with two rotary switches and a large backlight display which enables multiple results to be displayed simultaneously. A graphical quick start guide is provided inside the lid of each model to assist first time users.
Safety of operation is built in, 5 kV and 10 kV models are safety rated to CAT IV 600 V up to 3000 m and the 15 kV S1-1568 is rated at CAT IV 1000 V up to 4000 m. Original equipment manufacturers and repairers will welcome the remote control feature allowing them to automate resistance testing on the factory floor, as will technicians in substations wanting to operate from a more convenient, safe distance.
he S1-Series have a dual case design with a tough outer case to protect the tester from knocks and drops and a fire retardant inner case. The case IP rating prevents moisture and dust ingress when storing or carrying the instrument. The lids have clip-on lead pouches ensuring that leads remain with the instrument at all times. Case lids are removable for improved access to the terminals.
Five preset voltage ranges are provided in insulation test mode, plus a user settable lock voltage range. Preconfigured diagnostic tests include Polarisation Index (PI), Dielectric Absorption Ratio (DAR), Dielectric Discharge (DD), Stepped Voltage (SV) and Ramp test.
Advanced memory storage includes time/date stamping of results, logging of data and recall of results to screen. A fully isolated USB interface or on-board Bluetooth® interface is used for safe transfer of data to Megger’s asset management software; PowerDB Pro, Advanced or Lite packages.
Test leads are double insulated with clamps rated at 3 kV tequivalent to 6 kV single insulation for the medium clip leadset and 5 kV t equivalent to 10 kV single insulation for the large clip. The 15 kV leadset is insulated to 15 kV.
APPLICATION
The Insulation Resistance (IR) test is a quantitative test which indicates the effectiveness of a product’s electrical insulation. Applications include cables, transformers, motors/generators, circuit breakers and bushings. Common insulation tests are the “spot test”, a 1 minute IR test and a 10 minute Polarisation Index (PI) test, where PI is the ratio R10min / R1min and is temperature independent.
Features and benefits
- Resistance measurement: 15 TΩ - 5 kV,
- 35 TΩ - 10 kV, 35 TΩ - 15 kV
- High current – 6 mA short circuit current
- High noise immunity – 8 mA of noise rejection
- Four software filters: 10 s, 30 s, 100 s, 200 s
- Li-ion battery – charges in 2 hours and gives up to 6 hours continuous testing a 100 MΩ load (S1-568), battery meets IEC 62133
- Remote operation via USB cable
- Download of memory via isolated USB cable Bluetooth®
- IR, timed IR, DAR, PI, DD, SV and ramp diagnostic tests
- Large LCD display with backlight
- Dedicated voltmeter function (30 V to 660 V) AC or DC
- Advanced memory, on screen recall and real time clock for date/ time stamped results
- PowerDB Lite asset management compatabilty
- Option to record temperature and/or relative humidity with saved results (measured independently)
AC
voltage (auto ranging) |
|
S1-568 | 90 - 264 V rms,50/60 Hz, 100 A |
Battery life |
11.1 V, 5.2Ah meets IEC
62133:2003 (S1-1568 has 2 batteries) |
S1-568 |
6 hours (typical) continuous testing at 5 kV with a 100 MΩ load |
30 min quick charge | 1 hour operation at 5 kV with a
100 MΩ load |
Battery charge time |
.5 hours deep discharge,2 hours
normal discharge |
Test voltage |
50 V, 500 V, 1000 V, 2500 V,
5000 V |
Lock test voltage |
0 V to 1 kV in 10 V steps,1 kV
to 5 kV in 25 V steps,5 kV to 15 kV in 25 V steps |
Test voltage accuracy |
+4%, -0%, ±10 V nominal test
voltage at 1 GΩ load (0°C to 30°C) |
Resistance range |
10 k to 15 TΩ @ 5 kV, 10 k to 35
TΩ @ 10 kV, 10 k to 35 TΩ @ 15 kV |
Accuracy |
10 kV 5000 V 2500
V 1000 V 500 V ±5% to 1 TΩ 500 GΩ 200 GΩ 100 GΩ 50 GΩ ±20% to 10 TΩ 5 TΩ 2 TΩ 1 TΩ 500 GΩ |
Guard terminal performance |
Guards out parallel leakage
resistance down to 250 kΩ with a maximum additional resistance error of
1% with a 100 MΩ load |
Display range analogue |
100 kΩ to 10 TΩ |
Display range digital: |
10 kΩ to 35 TΩ |
Short circuit/charge current |
6 mA |
Insulation test Alarm |
100 kΩ to 10 GΩ |
Capacitor charge |
(on battery): < 2.5 s/μF to 5 kV <5 s/μF to 10 kV < 6.3 s/μF to 15 kV (with AC): < 1.5 s/μF to 5 kV , <2.7 s/μF to 10 kV, < 4 s/μF to 15 kV |
Capacitor discharge |
5 kV to 50 V :< 120 ms/μF 10 kV to 50 V:< 250 ms/μF 15 kV to 50 V:< 3500 ms/μF |
Capacitance range With test voltage set above 500V |
10 nF to 25 μF |
Capacitance measurement accuracy |
10 nF to 10 μF : ±10% ±5 nF |
Current range |
0.01 nA to 6 mA |
Interference |
8 mA from 1200 V to 2500 V |
Software 4 filter settings |
10 s, 30 s, 100 s, 200 s |
Voltmeter range |
30 V to 660 V ac or dc, 45Hz –
65Hz |
Voltmeter accuracy |
±3%, ±3V |
Timer range |
Up to 99 minutes 59 seconds,15
second minimum setting |
Memory capacity |
11 hrs logging @ 5 sec intervals |
Test modes |
IR, IR(t), DAR, PI, SV, DD, ramp
test |
Interface |
USB type B (device), Bluetooth®
Class 2 |
Real time output |
(V, I, R) readings at a rate of
1 Hz |
Remote control |
Remote control via USB cable
only(requires RC dongle to be in position) |
ENVIRONMENTAL | |
Maximum altitude | 3000 m |
Operating temperature range |
-20 °C to 50 °C |
Storage temperature range |
-25 °C to 65 °C |
Humidity |
90% RH non-condensing at 40 °C |
IP rating |
IP65 (lid closed), IP40 (lid
open) |
Safety |
Meets the requirements of IEC
61010-1,CATIV 600 V to 3000 m (5 kV, 10 kV)CATIV 1000 V to 4000 m (15
kV) |
EMC |
Meets the requirements of
IEC61326-1 |
Dimensions |
285 mm x 181 mm x 315 mm |
Weight | 4,5 kg |
For full Megger S1-568 Insulation Tester product specifications, please click here: Megger S1-568