Megger DET14C Earth/Ground Clamp-On Resistance Tester

$1,995.00
Availability: In stock
SKU
2C113

Condition: Refurbished / Calibrated

Warranty: 1 YEAR WARRANTY

Shipping: USA & Worldwide

  • Megger DET14C Earth/Ground Clamp-On Resistance Tester (BC# -L/T*)
Request a Quote for

Have questions or doubts? Submit the following request and expect our detailed quote within 24 hours!

We are commited to win your business!

Megger DET14C Earth/Ground Clamp-On Resistance Tester

The Megger DET14C is a clamp-on tester used to check the resistance of an earth or ground connection. It helps electricians and maintenance technicians assess grounding systems at sites such as substations, utility installations, and industrial facilities.

To take a reading, the user closes the clamp around a grounding conductor or strap. The DET14C induces a test current and measures the resulting resistance without requiring ground stakes or disconnecting the connection. This makes routine checks quicker in installations with multiple grounding paths.

The instrument measures ground resistance from 0.05 Ω to 1,500 Ω. It also measures true RMS ground leakage current from 0.5 mA to 35 A, helping technicians identify current flowing through a grounding conductor.

Its elliptical jaws fit cables up to 37 mm in diameter or ground straps up to 50 mm wide. A backlit display supports work in dim locations, while the flat jaw surfaces help reduce dirt buildup. The DET14C has a CAT IV 600 V safety rating and can store results for later review on its screen.

The clamp-on method requires multiple connected grounds to provide a return path for the test current. It cannot measure an isolated ground electrode on its own. When used on a suitable system, the DET14C provides a convenient way to check grounding resistance and leakage current during inspections and preventive maintenance.


Features:

  • Clamp-on ground resistance testing without disconnecting the ground connection
  • Ground resistance measurement from 0.05 Ω to 1,500 Ω
  • True RMS ground leakage current measurement from 0.5 mA to 35 A
  • Elliptical jaws that fit cables up to 37 mm in diameter or ground straps up to 50 mm wide
  • Flat jaw surfaces designed to reduce dirt buildup
  • Built-in filter to help with electrical interference
  • Backlit LCD for low-light conditions
  • Onboard storage with on-screen recall of results
  • CAT IV 600 V safety rating

 

Category Specification Megger DET14C
Product Type Digital clamp-on earth/ground resistance tester
Product Order code 1000-761
Test method Ground resistance Clamp-on, stakeless; requires a multi-ground system with a return path
Ground resistance Measurement range 0.05–1,500 Ω
Ground resistance Measurement frequency 1,390 Hz
Leakage current Measurement type True RMS AC
Leakage current Measurement range 0.5 mA–35.0 A RMS
Leakage current Measurement frequency range 16–400 Hz
Clamp Maximum jaw opening 39 mm
Clamp Maximum jaw interior dimensions 39 × 55 mm
Clamp Cable or strap capacity Cable up to 37 mm diameter; ground strap up to 50 mm wide
Display Type Backlit LCD
Measurement Range selection Automatic within each mode
Measurement Sampling time Less than 1 second
Data storage Capacity 256 records
Data transfer Bluetooth No; Bluetooth transfer is a DET24C feature
Alerts Functions High and low alarms; audible warning
Power Batteries Four 1.5 V AA alkaline batteries
Battery life Continuous testing Approximately 24 hours under the datasheet’s stated test conditions
Auto power-off Time 300 seconds
Safety Rating CAT IV 600 V
Ingress protection Rating IP30 with jaws closed
Operating conditions Temperature −20 to +50 °C
Dimensions Length × width × height 248 × 114 × 49 mm
Weight Instrument 985 g