Megger DET14C Earth/Ground Clamp-On Resistance Tester
Condition: Refurbished / Calibrated
Warranty: 1 YEAR WARRANTY
Shipping: USA & Worldwide
- Megger DET14C Earth/Ground Clamp-On Resistance Tester (BC# -L/T*)
Megger DET14C Earth/Ground Clamp-On Resistance Tester
The Megger DET14C is a clamp-on tester used to check the resistance of an earth or ground connection. It helps electricians and maintenance technicians assess grounding systems at sites such as substations, utility installations, and industrial facilities.
To take a reading, the user closes the clamp around a grounding conductor or strap. The DET14C induces a test current and measures the resulting resistance without requiring ground stakes or disconnecting the connection. This makes routine checks quicker in installations with multiple grounding paths.
The instrument measures ground resistance from 0.05 Ω to 1,500 Ω. It also measures true RMS ground leakage current from 0.5 mA to 35 A, helping technicians identify current flowing through a grounding conductor.
Its elliptical jaws fit cables up to 37 mm in diameter or ground straps up to 50 mm wide. A backlit display supports work in dim locations, while the flat jaw surfaces help reduce dirt buildup. The DET14C has a CAT IV 600 V safety rating and can store results for later review on its screen.
The clamp-on method requires multiple connected grounds to provide a return path for the test current. It cannot measure an isolated ground electrode on its own. When used on a suitable system, the DET14C provides a convenient way to check grounding resistance and leakage current during inspections and preventive maintenance.
Features:
- Clamp-on ground resistance testing without disconnecting the ground connection
- Ground resistance measurement from 0.05 Ω to 1,500 Ω
- True RMS ground leakage current measurement from 0.5 mA to 35 A
- Elliptical jaws that fit cables up to 37 mm in diameter or ground straps up to 50 mm wide
- Flat jaw surfaces designed to reduce dirt buildup
- Built-in filter to help with electrical interference
- Backlit LCD for low-light conditions
- Onboard storage with on-screen recall of results
- CAT IV 600 V safety rating
| Category | Specification | Megger DET14C |
|---|---|---|
| Product | Type | Digital clamp-on earth/ground resistance tester |
| Product | Order code | 1000-761 |
| Test method | Ground resistance | Clamp-on, stakeless; requires a multi-ground system with a return path |
| Ground resistance | Measurement range | 0.05–1,500 Ω |
| Ground resistance | Measurement frequency | 1,390 Hz |
| Leakage current | Measurement type | True RMS AC |
| Leakage current | Measurement range | 0.5 mA–35.0 A RMS |
| Leakage current | Measurement frequency range | 16–400 Hz |
| Clamp | Maximum jaw opening | 39 mm |
| Clamp | Maximum jaw interior dimensions | 39 × 55 mm |
| Clamp | Cable or strap capacity | Cable up to 37 mm diameter; ground strap up to 50 mm wide |
| Display | Type | Backlit LCD |
| Measurement | Range selection | Automatic within each mode |
| Measurement | Sampling time | Less than 1 second |
| Data storage | Capacity | 256 records |
| Data transfer | Bluetooth | No; Bluetooth transfer is a DET24C feature |
| Alerts | Functions | High and low alarms; audible warning |
| Power | Batteries | Four 1.5 V AA alkaline batteries |
| Battery life | Continuous testing | Approximately 24 hours under the datasheet’s stated test conditions |
| Auto power-off | Time | 300 seconds |
| Safety | Rating | CAT IV 600 V |
| Ingress protection | Rating | IP30 with jaws closed |
| Operating conditions | Temperature | −20 to +50 °C |
| Dimensions | Length × width × height | 248 × 114 × 49 mm |
| Weight | Instrument | 985 g |