The DM-IIIS represents a new approach to the world of electrical measurement. Computer assisted instruments such as the DM-IIIS permit an easy and fast analysis of a huge quantity of data.
The DM-IIIS is able to:
Voltage anomoalies detection (manual selection of range)
Voltage
Time
Current measurement (using external transducer)
Minimal Current measurable is equal to 0.5% of Clamp Full Scale
Power measurement (cosf: 0.5c ヨ 0.5i)
Cosf measurement
Harmonics measurement
Voltage
The voltage harmonics will be null under the following threshold:
- DC: if <1V or <2% of 1st harmonic
- 1st harmonic: if <2V
- 2nd divided by 49th: if <1V or <2% 1st harmonic
Current
The voltage harmonics will be null under the following threshold:
- DC: if <2% of 1st harmonic or <0,2% of clamp full scale
- 1st harmonic: if < 0,2% of clamp full scale
- 2nd Divided by 49th: if <2% 1st harmonic or <0,2% of clamp full scale
Setting the FLEX option the DC componenet will be ignored
Frequency measurement
Instrument set to 50Hz
Instrument set to 60Hz
General Specifications
For full Amprobe DM-III specifications, please click here: Amprobe DM-III
The DM-IIIS represents a new approach to the world of electrical measurement. Computer assisted instruments such as the DM-IIIS permit an easy and fast analysis of a huge quantity of data.
The DM-IIIS is able to:
- Display in real time the electrical parameters of a single phase and three-phase systems (with or without neutral wire) and the harmonic analysis of voltages and currents
- Conduct a direct Energy measurement (without memorizing).
- Memorize (pressing SAVE key) the sampled values of the Parameters present at the instrumentメs input generates a "Smp" record inside the instrumentメs memory. It will be possible to analyze the memorized data ONLY by transferring it to a PC.
- Record simultaneously (pressing the START key after a proper setting): RMS values of voltages, currents, corresponding harmonics, active, reactive and apparent powers, power factors and cos?, active, reactive and apparent energies, voltage sag and surge with 10ms resolution. It will be possible to analyze the recorded data ONLY by transferring them to a PC.
Range | Accuracy | Resolution | Input impedance |
15-370V | ±(0.5%+2digit) |
0.2V | 300kO (phase-neutral) 600kO (phase-phase) |
310-635V | 0.4V |
Voltage anomoalies detection (manual selection of range)
Voltage
Range | Accuracy | Resolution | Input impedance |
15-370V | ±(0.5%+2digit) |
0.2V | 300kO (phase-neutral) 600kO (phase-phase) |
30-635V | 0.4V |
Time
Accuracy (ref. to 60Hz) | Resolution |
±8.33ms (½ period of fundamental) | 8.33ms (½ period of fundamental) |
Current measurement (using external transducer)
Range | Accuracy | Resolution | Input impedance | Protection against overloads |
0.005-0.26V | ±(0.5%+2digit) |
0.0001V | 100kO for STD or FlexEXT 8.3kO for FlexINT (1000A) 9.4kO for FlexINT (3000A) |
5V |
0.26-1V | 0.0004V |
Power measurement (cosf: 0.5c ヨ 0.5i)
Value | Ranges | Accuracy | Resolution |
Active power | 0 ヨ 999.9W 1KW ヨ 999.9KW 1MW ヨ 999.9MW |
±(1.0%+2digit) |
0.1W 0.1KW 0.1MW |
Reactive power | 0 ヨ 999.9VAR 1KVAR ヨ 999.9KVAR 1MVAR ヨ 999.9MVAR |
0.1VAR 0.1KVAR 0.1MVAR |
|
Apparent power | 0 ヨ 999.9VA 1KVA ヨ 999.9KVA 1MVA ヨ 999.9MVA |
0.1VA 0.1KVA 0.1MVA |
|
Active energy | 0 ヨ 999.9Wh 1KWh ヨ 999.9KWh 1MWh ヨ 999.9MWh |
0.1Wh 0.1KWh 0.1MWh |
|
Reactive energy | 0 ヨ 999.9VARh 1KVARh ヨ 999.9KVARh 1MVARh ヨ 999.9MVARh |
0.1VARh 0.1KVARh 0.1MVARh |
Cosf measurement
Cosf | Resolution | Uncertainty (expressed in degrees) |
0.20 | 0.01 |
1.0 |
0.50 | 0.7 | |
0.80 | 0.6 |
Harmonics measurement
Voltage
Range | Accuracy | Resolution |
DC ヨ 25h 26h ヨ 33h 34h ヨ 49h |
±(5.0%+2digit) ±(10.0%+2digit) ±(15.0%+2digit) |
0.1V |
- DC: if <1V or <2% of 1st harmonic
- 1st harmonic: if <2V
- 2nd divided by 49th: if <1V or <2% 1st harmonic
Current
Range | Accuracy | Resolution |
DC ヨ 25h 26h ヨ 33h 34h ヨ 49h |
±(5.0%+2digit) ±(10.0%+2digit) ±(15.0%+2digit) |
0.1A |
- DC: if <2% of 1st harmonic or <0,2% of clamp full scale
- 1st harmonic: if < 0,2% of clamp full scale
- 2nd Divided by 49th: if <2% 1st harmonic or <0,2% of clamp full scale
Setting the FLEX option the DC componenet will be ignored
Frequency measurement
Instrument set to 50Hz
Range | Resolution | Accuracy |
47 ÷ 53 | 0,1 Hz | ±(1.0%+1digit) |
Instrument set to 60Hz
Range | Resolution | Accuracy |
57 ÷ 63,6 | 0,1Hz | ±(1.0%+1digit) |
General Specifications
Mechanical features | |
Dimensions: | 8.9ヤ(L) x 6.5ヤ (La) x 4.1ヤ(H) 225(L) x 165(La) x 105(H) mm |
Weight: | 3.3 Lb (1.5kg) |
Internal power supply | 6 batteries 1.5V series AA LR6 |
Battery Life: | 50 hours |
External power supply | Use only Amprobe power supply Adapter code DMT-EXTPS |
Display: | dot matrix with backlight |
Resolution | 128 x 128 dots (16384 dots) |
Dot size | 0.5mm x 0.5mm |
Visible area | 2.9ヤ x 2.9ヤ (73mm x 73mm) |
Sampling speed: | 130.21usec a 60Hz. |
No. of samples per period | 128 |
Clamp (FLEX3) | |
Maximum diameter of the cable: | 5.9ヤ (150 mm) |
Operating conditions | |
Reference temperature: | 73°F ± 2°F (23°C ± 1°C) |
Operating temperature: | 32°F to 122°F (0°C to 50 °C) |
Relative humidity: | <70% |
Storage temperature: | 14°F to 140°F (-10°C to 60 °C) |
Storage humidity: | <80% |
For full Amprobe DM-III specifications, please click here: Amprobe DM-III
Amprobe DM-III S Three Phase Power Quality Recorder
Display in real time the electrical parameters of a single phase and three-phase systems (with or without neutral wire) and the harmonic analysis of voltages and currents
Includes (3) Amprobe DM-CT-HT Current Clamps, Carrying Case & Accessories As Listed
DMIII S DM III
Amprobe DM-III S DM III S Power Quality Recorder Models On Sale Warranty Calibration Backed by The Best Service and Lowest Prices in the Industry.
BC# 15943
- Amprobe DM-III S Digital Recorder (BC# 15943)
- (3) Amprobe DM-CT-HT Current Clamps
- (4) Amprobe Test Leads w/ Alligator Clips
- AC Adapter/Charger
- Power Cord
- RS232 PC Interface Cable
- User Manual On CD-ROM
- Carrying Case w/ Strap