AEMC 8335 PowerPad 3 Phase Power Quality Analyzer
$3,995.00
Availability:
Out of stock
SKU
PQ13
Condition: Refurbished / Calibrated
Warranty: 90 Day Exchange
Shipping: USA & Worldwide
Request a Quote for
- AEMC 8335 PowerPad Three-Phase Power Quality Analyzer (BC# 29550-L/T*)
- (4) AEMC MN93 Current Clamps
- (5) AEMC Flexible Test Leads
- (4) Alligator Clips
- AC Adapter/Charger
- (2) Power Cords
- USB PC Interface Cable
- Hard Copy User Manual
- Case For Unit
- Carrying Case w/ Strap
AEMC 8335 Power Pad
The PowerPad® Model 8335 is a three-phase power quality analyzer that is easy-to-use, compact and shock-resistant. It is intended for technicians and engineers to measure and carry out diagnostic work and power quality work on one, two or three phase low voltage networks.
The PowerPad®メs 2GB of memory is conveniently partitioned to let you store four different types of data, synchronized or independent of each other. You can store up to 50 screen snapshots, up to 300 captured transients that contain four cycles for each active input, and 10000 alarm events from up to 40 different parameters. You can also record trend data for days, weeks or even months.
Six direct access function buttons quickly let you see:
Waveforms ヨ Display Volts, Amps, THD and Crest Factor by phase or for all phases. You can display all the voltage inputs on one screen, phase-to-phase or phase-to-neutral. Realtime phasor diagrams can be displayed for volts and amps, also by phase or for all phases including phase unbalance.
Harmonics ヨ Display Harmonics out to the 50th for Volts, Amps and VA. Individual Harmonics
are displayed as a percentage and value for Volts, Amps and VA. Harmonic direction and
sequencing can also be displayed.
Transients ヨ Set, capture and display transients. You select the threshold and the number of transients to capture. The PowerPad® then captures four waveforms for each transient; the triggering waveform as well as one pre-triggered and two post-triggered waveforms. As many as 300 transients each consisting of 4 waveforms per channel for up to 8 channels can be captured.
Trend Recording ヨ Record and display trend data at user selectable sample rates from 1/sec to 1/15 minutes and user programmable recording periods into 2GB of memory.
Specifications:
For full AEMC 8335 product specifications, please click here: AEMC 8335
The PowerPad® Model 8335 is a three-phase power quality analyzer that is easy-to-use, compact and shock-resistant. It is intended for technicians and engineers to measure and carry out diagnostic work and power quality work on one, two or three phase low voltage networks.
The PowerPad®メs 2GB of memory is conveniently partitioned to let you store four different types of data, synchronized or independent of each other. You can store up to 50 screen snapshots, up to 300 captured transients that contain four cycles for each active input, and 10000 alarm events from up to 40 different parameters. You can also record trend data for days, weeks or even months.
Six direct access function buttons quickly let you see:
Waveforms ヨ Display Volts, Amps, THD and Crest Factor by phase or for all phases. You can display all the voltage inputs on one screen, phase-to-phase or phase-to-neutral. Realtime phasor diagrams can be displayed for volts and amps, also by phase or for all phases including phase unbalance.
Harmonics ヨ Display Harmonics out to the 50th for Volts, Amps and VA. Individual Harmonics
are displayed as a percentage and value for Volts, Amps and VA. Harmonic direction and
sequencing can also be displayed.
Transients ヨ Set, capture and display transients. You select the threshold and the number of transients to capture. The PowerPad® then captures four waveforms for each transient; the triggering waveform as well as one pre-triggered and two post-triggered waveforms. As many as 300 transients each consisting of 4 waveforms per channel for up to 8 channels can be captured.
Trend Recording ヨ Record and display trend data at user selectable sample rates from 1/sec to 1/15 minutes and user programmable recording periods into 2GB of memory.
Specifications:
Electrical | |||
Sampling Frequency | 256 samples per cycle | ||
Data Storage | 2GB SD Card | ||
Voltage (TRMS) | Phase-to-Phase: 1000V; Phase-to-Neutral: 1000V | ||
Current (TRMS) | MN Clamp: 0 to 6A/120A or 0 to 240A SR Clamp: 0 to 1200A MR Clamp: 0 to 1000AAC, 0 to 1400ADC MiniFlexル: 0.1 to 1000A AmpFlex®: 0 to 6500A1 |
||
MEASUREMENT | RANGE | RESOLUTION | ACCURACY |
Single-Phase RMS Voltages | 15 to 1000V | 0.1V | ±0.5% ± 2cts |
Phase-to-Phase RMS Voltages | 15 to 1000V | 0.1V | ±0.5% ± 2cts |
DC Voltage Component | 15 to 1000V | 0.1V | ±1% ± 5cts |
Single-Phase Peak Voltages | 15 to 1414V | 0.1V < 1000V 1V > 1000V |
±(1% + 1V) |
Phase-to-Phase Peak Voltages | 15 to 1414V | 0.1V < 1000V 1V > 1000V |
±(1% + 1V) |
Frequency (Hz) | 40 to 69Hz | 0.01Hz | ±0.01Hz |
Current Probes (Arms) MN Probe SR Probe AmpFlex® Sensor |
0 to 240A 0 to 1200A 10 to 6500A |
0.1A 0.1A < 1000V; 1A > 1000A 0.1A < 1000V; 1A > 1000A |
±(0.5% + 2cts) ±(0.5% + 2cts); ±(0.5% + 1ct) ±(0.5% + 1A) |
Active (Real) Power (kW) | 0 to 9999kW | 4 digits (10,000ct) | ±1% ± 1ct @ PF =0.8 |
Reactive Power (kVAR) | 0 to 9999kVAR | 4 digits (10,000ct) | ±1% ± 1ct @ PF =0.8 |
Apparent Power (kVA) | 0 to 9999kVA | 4 digits (10,000ct) | ±1% ± 1ct |
Power Factor (PF & DPF) | -1.000 to 1.000 | 0.001 | ±(1.5% + 10cts) |
Active Energy (kWh) | 0 to 9999MWh | 4 digits (10,000ct) | ±1% ± 1ct @ PF =0.8 |
Reactive Energy (kVARh) | 0 to 9999MVARh | 4 digits (10,000ct) | ±1% ± 1ct @ PF =0.8 |
Apparent Energy (kVAh) | 0 to 9999MVAh | 4 digits (10,000ct) | ±1% ± 1ct |
Unbalance (V & A) | 0 to 100% | 0.1% | ±1% ± 1ct |
Phase Angle (VヨA, AヨA, VヨV) | -179° to +180° | 1° | ±2° ± 1ct |
Harmonics (1st to 50th) F = 40 to 69Hz (V = 50V, A > nom/100) |
0 to 999% | 0.1% | ±1% + 5cts |
Total Harmonic Distortion (V & A) | 0 to 999% | 0.1% | ±1% + 5cts |
K-factor (Akf) | 1 to 99.99 | 0.01 | ±5% ± 1ct |
Flicker (Pst) | 0.00 to 9.99 | 0.01 | - |
Power Source | 9.6V NiMH rechargeable battery pack External AC supply: 110/230VAC ±10% (50/60Hz) |
||
Battery Life | =8 hrs with display on; =35 hrs with display off (record mode) | ||
Mechanical | |||
Dimensions | 9.8 x 7.8 x 2.6" (250 x 200 x 67mm) | ||
Weight | 4.3 lbs (1.95kg) | ||
Display | |||
Display Type | 1/4 VGA (320 x 240) color LCD | ||
Environmental | |||
Operating Temperature | 32° to 122°F (0° to 50°C) | ||
Storage Temperature | -4° to +122°F (-20° to +50°C) |
For full AEMC 8335 product specifications, please click here: AEMC 8335